background image

- 5 -

GAS INLET & MANIFOLD PRESSURES

Input Minimum

Input Maximum

Manifold Pressure

NATURAL

LP (Propane)

11" wc

13" wc

10" wc

4.5" wc

7" wc

3.5" wc

1/2" GAS SUPPLY

1/2" X 3/8" REDUCER

3/8" NIPPLE

3/8" NIPPLE

3/8" NIPPLE

3/8" X 3/8" SHUT OFF VALVE

3/8" UNION

DO NOT USE THIS FIREPLACE IF ANY PART
OF THIS FIREPLACE HAS BEEN UNDER
WATER.  IMMEDIATELY CALL A QUALIFIED
SERVICE TECHNICIAN TO INSPECT THE
HEATER AND TO REPLACE ANY PART
CONTROL WHICH HAS BEEN UNDER
WATER.

When using copper or flex connector use only approved
fittings. Always provide a union when using black iron
pipe
 so that gas line can be easily disconnected for burner
or fan servicing. See Fig. 2.  See gas specification for
pressure details and ratings.

The fireplace valve must not be subjected to any test
pressures exceeding 1/2 psi. Isolate or disconnect this or
any other gas appliance control from the gas line when
pressure testing.

Al

ways check for gas leaks with a mild soap and

water solution.  Do not use an open flame for
leak testing.
The gas control is equipped with a captured
screw type pressure test point, therefore it is not
necessary to provide a 1/8" test point up stream
of the control.

FOR U.S.A Installations

 consult the current National

Fuel Gas Code, ANSI Z223.1

GAS LINE INSTALLATION

When purging gas line, the front glass must
be removed.

The gas pipeline can be brought in through the rear of the
fireplace as well as the bottom.  Knockouts are provided on
the bottom behind the valve to allow for the gas pipe
installation and testing of any gas connection. It is most
convenient to bring the gas line in from the rear right
side of the valve, as this allows fan installation or
removal without disconnecting the gas line.

The gas line connection can be made with
properly tinned 3/8" copper tubing, 3/8" rigid
pipe or an approved flex connector. Since
some municipalities have some additional
local codes, it is always best to consult your
local authority and the CAN/CGA- B149 (.1 or
.2) installation code.

PREPARATION

The use of wall paper adjacent to this fire-
place is not recommended, as the high heat
given off by this fireplace may adversely
effect the binders in the adhesive used to
apply the wallpaper.

Before beginning, remove the glass door from the fireplace
(See page 9).  Also check to make sure there is no hidden
damage to the fireplace.  Take a minute and plan out the
gas, vent and electrical supply.

Fig. 2 

 Typical gas supply installation

GAS SPECIFICATIONS

MAX.

MIN.

INPUT

 INPUT

MODEL

FUEL

GAS CONTROL B.T.U.H

B.T.U.H.

RFS22RN

Natural Gas

Millivolt Hi/Lo

30,000

21,000

RFS22RP

Propane Gas

Millivolt Hi/Lo

30,000

22,500

RFS22TN

Natural Gas

Thermostatic

30,000

21,000

RFS22TP

Propane Gas

Thermostatic

30,000

22,500

RFS32RN

Natural Gas

Millivolt  Hi/Lo

30,000

21,000

RFS32RP

Propane Gas

Millivolt  Hi/Lo

30,000

22,500

RFS32TN

Natural Gas

Thermostatic

30,000

21,000

RFS32TP

Propane Gas

Thermostatic

30,000

22,500

RFS42RN

Natural Gas

Millivolt Hi/Lo

40,000

28,000

RFS42RP

Propane Gas

Millivolt Hi/Lo

37,000

27,750

RFS42TN

Natural Gas

Thermostatic

40,000

28,000

RFS42TP

Propane Gas

Thermostatic

37,000

27,750

The installation of your Majestic Fireplace
must conform with local codes, or in the
absence of local codes, with National Fuel
Gas Code, ANSI Z223.1 latest edition, or CAN
1 B1-149.1 and .2 Installation Code.
(EXCEPTION:  Do not derate this appliance
for elevations up to 4,500 ft. (1,370mm).
Maintain the manifold pressure at 3.5 inches
W.C. for Natural Gas and 10 inches W.C. for
LP gas.)

ANSI.Z21.88a-1998 / CSA 2.33a - M98

Vented Gas Fireplace Heaters

RFS22 / RFS32 / RFS42

CERTIFIED TO

Summary of Contents for RFS22

Page 1: ...llow the gas suppliers instructions If you cannot reach your gas supplier call the fire department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE FOR YOUR SAFETY Installation and service must be performed by a qualified installer Service agency or your gas supplier Free Standing Fireplaces RFS...

Page 2: ...n 5 Gas Line Installation 5 Installation of Remote Switch for RN RP gas valve 6 Fan Kit 6 General Venting Information 7 Common Flue Installation 7 Retrofitting to an Existing Brick Chimney 8 Vent Safety System 8 Proper Vent Performance 8 Combustion Air 8 Operating Instructions 9 General Glass Information 9 Louvre Removal 9 Trim Removal 9 Glass Removal 9 Glass Cleaning 10 Installation of Logs and B...

Page 3: ...ck for clothing nor should Christmas stock ings or decorations be hung in the area of it 9 Undernocircumstancesshouldanysolidfuels wood coal paper or cardboard etc be used in this fire place 10 The flow of combustion and ventilation air must not be obstructed in any way 11 When the fireplace is installed directly on carpeting vinyltileoranycombustiblematerialotherthanwood the fireplace must be ins...

Page 4: ...29 5 8 752mm J 9 229mm K 5 1 4 133mm L M N MODEL RFS32 A 26 660mm B 26 660mm C 15 1 4 387mm D 19 1 4 488mm E 18 5 8 473mm F 21 533mm G 31 1 2 800mm H 17 3 4 451mm I 29 5 8 752mm J 95 8 244mm K 5 1 4 133mm L M N MODEL RFS22 A 28 1 4 717mm B 28 1 4 717mm C 17 7 8 454mm D 22 3 4 578mm E F G H 22 3 4 578mm I 33 5 8 854mm J 10 5 8 270mm K 5 1 4 133mm L 36 3 8 924mm M 14 3 16 360mm N 17 3 8 441mm MODEL ...

Page 5: ...ting the gas line The gas line connection can be made with properly tinned 3 8 copper tubing 3 8 rigid pipe or an approved flex connector Since some municipalities have some additional local codes it is always best to consult your local authority and the CAN CGA B149 1 or 2 installation code PREPARATION The use of wall paper adjacent to this fire place is not recommended as the high heat given off...

Page 6: ...d Fig 7 3 Locate the fan speed control junction box on screw studs provided on base of the fireplace Tighten with 3 8 nuts provided 4 Install thermal sensor element on screw studs located to the right of the gas valve on the burner base 5 Plug in grounded service cord to a convenient wall receptacle THIS FAN ASSEMBLY COMES COMPLETELY WIRED TO ELIMINATE THE NEED FOR ELECTRICIANS THIS ELECTRICAL DEV...

Page 7: ...ng the full height of the chimney as it is mandatory in most jurisdictions that the chimney be lined Another option is 4 B vent directly off the fireplace Fig 9 11 going up to the chimney liner or up through the roof if no chimney exists VENTING INSTRUCTIONS CANADIAN INSTALLATIONS The venting system must be installed in accordance with the current CAN CGA B149 1 or 2 installation code and the auth...

Page 8: ...g blown back into room the Vent Safety Switch will automatically shut down the heater 4 Should the heater turn off wait approximately 10 15 minutes to allow for the switch to reset Check draft again If the smoke is not drawn into the draft hood turn the fireplace off and check the cause of lack of draft consult your dealer for expert advice VENT SAFETY SYSTEM This fireplace is equipped with a vent...

Page 9: ...REMOVAL RFS22 1 Remove frame window brass trim See Trim Removal section 2 Remove remaining bottom 3 8 nut at the bottom of the frame window 3 Remove frame window by pulling it forward and up RFS32 1 Remove frame window brass trim See Trim Removal section 2 Remove remaining bottom 3 8 nut fat the bottom of the frame window 3 Remove 3 8 nut from each side of the frame window Fig 14 4 Remove frame wi...

Page 10: ...hes Ensure log is secure Top logs must be placed properly into notches RFS42 1 Remove Bay Window assembly and Glass Frame see Glass Frame Removal section 2 Remove logs from packaging 3 Place rear log SR4 on rear bracket Ensure log is seated properly leveled and centered to the unit so it will not move from side to side and it is firmly positioned on the bracket 4 Slip front ember log SR1 down in t...

Page 11: ...back of the firebox 5 Take left or right side refractory and slide it along the side of the firebox and on top of the bottom support channel Be sure to slide it back to hold the centre piece in place and the leading edge faces forward 6 Fasten top tab support against the refractory to hold it in place 7 Repeat steps 5 and 6 for remaining side refactory 8 Insert refractory pieces into the Bay Windo...

Page 12: ...ass FrameRemovalinmanual 8 Visiblylocatepilotbythemainburner 9 Turnknobongascontrolcounterclockwise to PILOT C Useonlyyourhandtopushinorturnthegascontrol knob Neverusetools Iftheknobwillnotpushinorturn byhand donottrytorepairit callaqualifiedservice technician Applyingforceoranyattemptedrepairmay resultinafireorexplosion D Donotusethisfireplaceifanyparthasbeenunderwater Immediatelycallaqualifiedse...

Page 13: ...efective automatic valve Turn valve knob to Pilot Maintain flow to pilot millivolt operator meter should read greater than 10 mV If the reading is okay and the pilot does not stay on replace the gas valve Note An interrupter block not supplied must be used to conduct this test 3 Pilot burning no gas to A Sensing bulb not in proper Make sure sensing bulb is located in bracket on the lower burner Va...

Page 14: ...ct this test 3 Pilot burning no gas to A Wall switch or wires Check wall switch and wires for proper connections Jumper burner Valve knob ON defective wire across terminals at wall switch if burner comes on Wall Switch ON replace defective wall switch If okay jumper wires across wall switch wires at valve if burner comes on wires are faulty or connections are bad B Thermopile may not be 1 Be sure ...

Page 15: ... ADJUST PILOT FLAME HEIGHT ALL WIRING CONNECTIONS REPLACE THERMOPILE THERMOCOUPLE NEEDS A MINIMUM OF 14mV DEFECTIVE VALVE TURN TO PILOT METER SHOULD READ GREATER THAN 100 mV IF NOT REPLACE PILOT LIGHTS WITH PIEZO IGNITOR YES YES YES YES PILOT STAYS LIT PILOT LIGHTS MAIN BURNER SYSTEM OK START CHECK VALVE IS TURNED ON ON OFF SWITCH IS NOT TURNED ON WATCH FOR GROUNDED WIRES THERMOPILE NEEDS A MINIMU...

Page 16: ...17 Thermopile 53374 53374 53374 18 Electrode Ignitor w cable SIT 52465 52465 52465 19 Ignitor Piezo SIT 52464 52464 50932 20 Ignitor Piezo Honeywell 2000062 2000062 2000062 21a Valve SIT 820 Nat 52677 52677 52677 21b Valve SIT 820 Prop 52678 52678 52678 22 Extension Knob Hi Lo RN RP 10000165 10000165 55162 23 Extension Knob On Off SIT RN RP 10000166 10000166 55163 24a Valve Honeywell Nat 10001782 ...

Page 17: ...2 36 a b 37 39 46 45 39 43 41 42 it H I L O O F F P IL O T 25a b 48 47 40 14 33 38 42 39 34 35 39 43 33 49 26 1 COMPLETE LOG SET RFS22 RFS32 1b 1d 1e 1f 1a 1c 22 23 3a b 4 2 40 8 a b 12 17 16 L O H I PILOT ADJ P I L O T ON OFF 24 a b 20 10 a b 9 a b 1COMPLETELOGSETRFS42 1d 1f 1e 1c 1b 1a ...

Page 18: ... On Off Button Remote Control MRC2 Temperature Control Remote MRC3 Temperature Control w digital display 24 hour programmable clock IMT Wall Mounted Thermostat REMOTE CONTROL For units with RN RP valves OPTIONS ...

Reviews: