18
07/20
7101-802G
Figure 5.1
Figure 5.2
Termination
cap
Flex Adapter
A. Outside Air Kit
A source of air (oxygen) is necessary in order for combustion
to take place. Whatever combustion air is consumed by the
fire must be replaced. Air is replaced via air leakage around
windows and under doors. In homes that have tightly sealed
doors and windows, an outside air source is needed. An
optional Outside Air Kit is available.
Items Needed for Installation (not supplied)
• Needed for option two:
- 4 inch flex aluminum pipe, or if using alternate
material, then it shall be made from durable, non-
combustible, heat resistant material up to 350°F.
- Cut the pipe to the required length for your installation.
• Needed for both options:
- Phillips head screw driver
- 5/32 Allen Wrench
- Silicone sealant
Option One - Installation Instructions
1. Ensure existing access hole in fireplace will not be
covered by the outer can. Existing outside air intake hole
may be under at the rear or side of outer can. Outside
air may also enter down existing chimney chase in some
situations.
2. Level outer can and install appliance. After installing the
appliance in the outer can, seal the fireplace opening
and trim package with insulation to prevent air leakage
into the room.
Option Two - Installation Instructions
3. Ensure existing access hole in fireplace is sufficient to
feed the 4 inch flex.
4. After sliding can into fireplace, feed flex into cut opening
to obtain outside combustion air.
5. Level outer can and install appliance.
NOTE:
Do not use plastic wire ties that come with the kit
as they will melt. You may need to install the flex pipe into
the firebox first depending on installation. Attach flex to
adapter with at least 2 screws.
5
5
Appliance Set-Up
Fire Risk. Asphyxiation Risk.
Do not draw outside combustion air from:
• Wall, floor or ceiling cavity
• Enclosed space such as an attic or garage
• Close proximity to exhaust vents
or chimneys
Fumes or odor may result
WARNING
!
WARNING
!
Asphyxiation Risk.
Length of outside air supply duct shall NOT
exceed the length of the vertical height of the
exhaust flue.
• Fire will not burn properly
• Smoke spillage occurs when door is opened due to
air starvation.
WARNING
!
Asphyxiation Risk.
Outside air inlet must be located to prevent
blockage from:
• Leaves
• Snow or ice
• Other debris
Block may cause combustion air starvation
Smoke spillage may set off alarms or irritate sensitive
individuals.