Vermont Castings Dutchwest 2479 Operating Manual Download Page 8

8

Dutchwest Non-Catalytic Convection Heater

30002291

Fireplace Installations -  

Through the Fireplace

The Convection heater may be installed either without 
legs* as a fireplace insert, or with standard legs at-
tached - depending on the safety regulations that apply 
to your situation, the height of the fireplace opening and 
your own preference. For either situation, the chimney 
connector/positive connection kit extends back from the 
stove, enters the fireplace cavity, and turns upward.  It 
then passes through the fireplace damper opening and 
smoke chamber and connects to the chimney flue.
In such installations, a “positive connection” must be 
made to the chimney flue with a special kit available 
from your local dealer.  Also, special clearance and floor 
protection provisions must be observed.  These provi-
sions are discussed in the Clearance and Floor Protec-
tion sections respectively.

Wall Pass-Throughs

Whenever possible, design your installation so the con-
nector does not pass through a combustible wall.  If you 
must use a wall pass-through in your installation, check 
with your building inspector before you begin and con-
struct it in accordance with local building codes.  Also 
check with the chimney connector manufacturer for any 
specific requirements.
Accessories are available for use as wall pass-
throughs.  If using one of these, make sure it has been 
tested and listed for use as a wall pass-through.
All combustible material in the wall is cut away a suffi-
cient distance from the single-wall connector to provide 
the required 12” (305 mm) clearance for the connector.  
Any material used to close up the opening must be non-
combustible.
 The following wall pass-through methods may be ap-
proved in your area:  

 

 

 

•  Use a section of listed factory-built  chimney with a 
nine-inch clearance to combustibles.
•  Place a chimney connector pipe inside a ventilated 
thimble, which is then separated from combustibles 
by 6” (152 mm) of fiberglass insulating material. 

•  

If the stove is installed without legs, we recommend 

the use of noncombustible tiles or pavers as shims to 
allow air flow into the convection air inlets under the 
stove. Make sure not to block air slots instove bottom 
with shims or remove fan cover. 
• Place a chimney connector pipe inside a section of 
listed solid-insulated, factory-built chimney, with an 
inside diameter 2” (51 mm) larger than the chimney 
connector and having 1” (25 mm) or more of insula-
tion and maintaining a minimum 2 inch air space 
between the outer wall of the chimney and combus-
tibles. 

In Canada:

 The Canadian Standards Association has 

established different guidelines.  Figure 11 shows one 
method, in which all combustible material in the wall is 
cut away to provide the required 18” (450 mm) clear-
ance for the connector.  The resulting space must 
remain empty.

DO NOT CONNECT THE HEATER TO ANY AIR 
DISTRIBUTION DUCT OR SYSTEM

ST420

wall pass through

with noncombust

6/27/00   djt

Chimney Con-

nector

12” 

(305mm)

12” 

(305mm)

ST420

Fig. 10

  Wall pass-through enclosed with noncombustible 

materials.

ST421

hollow wall pass through

6/2/04  djt

18” (450mm) 

Empty Space 

All Around the 

Chimney Con-

nector

Sheet Metal 

Cover

(One side 

only)

ST421

Fig. 11

  Hollow wall pass-through.

Summary of Contents for Dutchwest 2479

Page 1: ...erating Manual If this heater is not properly installed operated and maintained a house re may result For safety follow all installation operation and maintenance directions Contact local building of...

Page 2: ...to cause cancer birth de fects and other reproductive harm California Health Safety Code Sec 25249 6 Table of Contents Speci cations 3 Installation 4 Clearances 10 Assembly 16 Operation 18 Maintenanc...

Page 3: ...in a more severe or more temper ate climate these gures may not apply Since so many variables affect performance consult your Dutchwest Authorized Dealer to determine realistic expectations for your h...

Page 4: ...ed to 1 a chimney complying with the requirements for Type HT chimneys in the standard for Chimneys Fac tory Built Residential Type and Building Heating Appli ance UL 103 or 2 a code approved masonry...

Page 5: ...nector The chimney connector is the single wall pipe or listed and approved double wall pipe that connects the stove to the chimney The chimney itself is a masonry or prefabricated structure that encl...

Page 6: ...elescoping joints with at least three sheet metal screws 3 Secure the chimney connector to the chimney In structions for various installations follow below 4 Con rm that the installed stove and chimne...

Page 7: ...back into the replace chimney The liner of the replace chimney should extend at least to the point at which the chimney connector enters the chimney Follow all the guidelines for installing a chimney...

Page 8: ...ngle wall connector to provide the required 12 305 mm clearance for the connector Any material used to close up the opening must be non combustible The following wall pass through methods may be ap pr...

Page 9: ...t 1 19 Refer to How to Determine if Alternate Floor Protection Materials are Acceptable section The oor protector may be covered with a decorative noncombustible material if desired Do not obstruct th...

Page 10: ...ion for Fireplace Installations with Standard Legs Fireplace installations with the standard legs and the bottom heat shield must have a oor protector of the same construction as that speci ed for fre...

Page 11: ...ombustible surface Keep furnish ings and other combustible materials away from the stove as well In general a distance of 48 1220 mm must be maintained between the stove and moveable combustible items...

Page 12: ...himney Connector Clearance Chart that follows For example the letter A gives the minimum side clear ance for installations in which the stove is not equipped with any heat shield and the wall beside t...

Page 13: ...m Double wall connector 10 8 ue collar heat shield 254 mm 216 mm Front Clearance to Combustibles All Installations 48 1219 mm Model 2479 Large Convection Heater UNPROTECTED SURFACES PROTECTED SURFACES...

Page 14: ...dutchwest flue centerline 6 30 00 djt A B C E D F C F Chimney Connector Side Rear Corner Side Rear Corner Listed Approved A 34 B 12 C 21 D 22 E 12 F 20 Double wall with 846 mm 318 mm 533 mm 572 mm 305...

Page 15: ...1219 mm 48 1219 mm Spaced 1 25 mm from Floor ST802 Fig 17 Sidewall protection ST803 corner wall protection 5 04 48 1219 mm 48 1219 mm Spaced 1 25 mm from Floor ST803 Fig 18 Corner wall protection Wall...

Page 16: ...ottom Heat Shield is required in many instal lations Refer to the oor protection information found in the Installation Section of this manual Attach the Legs and Heat Shield NOTE To avoid damaging the...

Page 17: ...ssen the effort of moving the stove over smooth ooring is to slide it on a piece of inverted carpet Move it slowly to ensure the oor is not scratched Retighten all leg fastening hardware ST815 back le...

Page 18: ...Opening the inlet shutters provides air for primary combustion To open the shutters turn the lever clockwise The shutters are all the way open when the lever points to ward the rear at a 9 00 positio...

Page 19: ...ulting in short burn time and dimin ished stove performance If you must burn it mix it in with greener wood to slow the burn Store your rewood under cover to keep it dry Even for short term storage ke...

Page 20: ...ase the ring rate of your heater by altering the air control adjustment range outlined in these directions In some newer homes that are well insulated and weather tight poor draft may result from insu...

Page 21: ...RT THE FIRE DO NOT BURN GARBAGE OR FLAM MABLE FLUIDS SUCH AS GASOLINE NAPTHA OR ENGINE OIL Also never use gasoline type lantern fuel kerosene charcoal lighter uid or similar liquids to start or freshe...

Page 22: ...ace in a metal container with a tight tting lid ST438 ash pail 7 6 00 djt ST438 ST805 remove ashes 5 04 ST805 Fig 28 Check the ash compartment before reloading the stove Safe Ash Handling Ashes may co...

Page 23: ...sen the small locking nut with an open end wrench 2 Use the allen wrench included with the stove to turn the striker screw clockwise one quarter turn and close the door to test the engagement The door...

Page 24: ...o 2 nuts on the threaded rods that secure the top plate to the inner top of the stove 2 Remove the top plate and open the damper 3 Loosen the adjusting bolt s lock nut Fig 32 4 Loosen the anchor bolt...

Page 25: ...e you inspect the chimney Use a ash light and mirror to sight up the ue through the chimney clean out door or chimney connector inspection tee If no inspection access is available disconnect the pipe...

Page 26: ...the system if nec essary ANNUAL SPRING CLEANING Disassemble the chimney connector and take it outdoors for inspection and cleaning Replace weak sections of connector Inspect the chimney for signs of d...

Page 27: ...ure from the high ue temperatures Because the insulation is less dense than masonry the inner steel liner warms up more quickly than a masonry chimney this makes the steel chimney support a good draft...

Page 28: ...n characteristics that adversely affect chimney draft also promote creosote condensation Consequently you can minimize creosote accumulation with an effective chim ney design and the use of operationa...

Page 29: ...more an art than a science Art in cludes technique and since installations homes and fuel vary the stove operator must also vary technique mostly timing to achieve satisfying results Over time you wil...

Page 30: ...reserves the right to make changes in design materials speci cations prices and discontinue colors and products at any time without notice Dutchwest Convection Heater Model 2479 Ref Description 2479...

Page 31: ...nt Door 30002177 Door Gasket Front Ash and Load Doors 1203589 26 Load Door Insulation 30002250 27 Load Door Refractory to June 2005 30002253 Load Door Refractory II replaces above 30002438 28 Handle w...

Page 32: ...e to the stove caused by burning salt saturated wood chemically treated wood or any fuel not recommended in the Owners Guide 4 This warranty does not cover a stove repaired by someone other than a Dut...

Reviews: