22
20306750
Designer Series Direct Vent Gas Fireplace
HORIZONTAL WITH VERTICAL RISE
(THROUGH-THE-WALL)
TERMINATION CONFIGURATIONS
Since it is very important that the venting system
maintain its balance between the combustion air
intake and the flue gas exhaust, certain limitations
as to vent configurations apply and must be strictly
adhered to.
The Vent Graph, showing the relationship between vertical
and horizontal side wall venting, will help to determine the
various dimensions allowable.
Figure 18
Minimum clearance between vent pipes and combustible
materials is 3" on top and 1" from bottom and sides unless
otherwise noted (Exception: Outside wall with firestop: 1"
all around pipes are allowed). If the vertical run is 7.5 feet
or more, from the floor of the fireplace, the clearance is 1"
on all sides of the horizontal run.
When vent termination exits through foundations less than
20" below siding outcrop, the vent pipe must be flush with
the siding.
It is best to locate the fireplace in such a way that minimizes
the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent
pipe from the flue collar of the fireplace (or the top of the
Transition Elbow) to the face of the finished outside wall
or the mounting flange of the termination.
•
The maximum number of 90° elbows per side wall
installation is three (3).
Figure 25
•
If a 90° elbow is fitted directly on the top of the fireplace,
the maximum horizontal vent run before the termination
or a vertical rise is 36” (914 mm).
Figure 26
•
If a 90° elbow is used in the horizontal vent run (level
height maintained) the horizontal vent length is reduced
by 36".
Figure 23.
This does not apply if the 90° elbows
are used to increase or redirect a vertical rise.
Figure
27
Example:
According to the vent graph (Page 19) the
maximum horizontal vent length in a system with a 7.5'
vertical rise is 20’ (6 m) and if a 90° elbow is required in the
horizontal vent it must be reduced to 17' (5.2 m).
In
Figures 27 and 28
dimension A plus B must not be
greater than 17' (5.2 m).
W
ARNING
When installing the appliance as a rear
vent unit, the 90° or 45° transition elbow
attached directly to the rear of the unit is
NOT INCLUDED in the following criteria
and calculations and, unless specifically
mentioned, should be ignored when
calculating venting layouts.
FP1176
max 90 bends
Figure 25 -
Maximum Three (3) 90°
Elbows Per Installation
3 x 90°
Elbows
3 x 90°
Elbows
FP1176
Max 20"
Max 20"
36"
(914 mm)
Max.
36"
(914 mm)
Max.
FP1177
max horizontal run
Figure 26 -
Maximum Horizontal Run
with No Rise
FP1177
7’6”
A
B
90°
FP2837
run reduction
FP2837
Figure 27 -
Horizontal Run Reduction
VENTING INSTALLATION