In the memory location menu the LED in the reader lights up briefly whenever a 
registered transponder key is recognized; however the relay does not pick up. If a 

non

-registered transponder key with the correct identification signal is recognised, 

the LED in the reader flickers, with other identification signals there is no reaction.

It is possible to quit the memory location menu at any time and return to the normal
operation mode by pressing the 

„P”

button for approx. one second.

You are also automatically returned to the normal operation mode if you are in the
memory location menu and between pressing buttons or between the transponder 
signals more than 90 seconds elapses.

3.2.1

Assigning a transponder key to the next free memory location

Change, if necessary, to the memory location menu (see 3.2).

Using the 

„+“

or 

„-“

buttons (see 3.2) (only necessary if you wish to register up to or

from a particular memory location number), alter the pre-setting of the next free memory
location.

Note

It is only possible to register a (as yet) non-registered transponder key if the selected 
memory location is free or deleted, i.e. the corresponding display must flash!

Hold the transponder key to be registered approx. 2 seconds in front of the reader 

the LED in the reader lights up briefly.

In as far as the transponder key to be registered has 

not

been assigned to any other

memory location in the decoder, the number of the memory location, under which the
transponder key has just been registered, appears as a static display.

Enter the name of the person, for which the transponder key has been registered, in the
list under the memory location number shown as a static display.

Proceed to register any other not yet registered transponder keys, as required.

If no further actions are to be carried out in the memory location menu (see 3.2), return
to the home position by pressing button 

„P“

for approx. one second.

3.2.2

Identifying and/or deregistering an available transponder key

Change, if necessary, to the memory location menu (see 3.2).

Hold the transponder key to be identified and/or deregistered approx. 2 cm in front of
the reader for one to two seconds 

the LED in the reader lights up briefly.

In as far as the transponder key to be identified and/or deregistered is registered in the
decoder, the number of the memory location now appears as a static display, under
which the available transponder key is stored.

The identification process is now completed. If no deregistration is to take place or no
further actions are to be carried out in the memory location menu (see 3.2), you can
return to the home position by pressing button 

„P“

for approx. one second.

If, however, the memory location of the transponder key just identified is to be deleted,
now  press the 

„+“

and 

„-“

buttons simultaneously for at least one second 

after-

wards the memory location number appears flashing because the memory location    

02.2008  TR30A058  RE

13

Summary of Contents for TER 1

Page 1: ...Transpondertaster TER1 Fitting and operating instructions Transponder key switch TER1 Notice de montage et d utilisation Touche r pondeuse TER1 Istruzioni per il montaggio e l uso Pulsante transponder...

Page 2: ...2 02 2008 TR30A058 RE Deutsch 3 English 10 Fran ais 17 Italiano 25 35 38...

Page 3: ...chl sseln Bis zu 100 Transponderschl ssel k nnen bei einem Auswerteger t angemeldet werden Lese und Auswerteger t werden durch eine einfache 2 adrige Leitung verbunden im Lieferzustand 5 m lang die bi...

Page 4: ...gt In der Regel sind dieses 2 A bitte beachten Sie aber die Angaben des jeweiligen T r ffners W hlen Sie im Zweifelsfall den n chst h heren Stromwert bei 12 V f r den einzusetzenden Transformator aus...

Page 5: ...it auf denen jeweils ein Transponderschl ssel angemeldet werden kann Mit Hilfe der zwei Siebensegmentanzeigen und der drei Taster kann berpr ft werden ob auf dem jeweiligen Speicherplatz ein Transpond...

Page 6: ...schl ssels auf den n chsten freien Speicherplatz Wechseln Sie ggf in das Speicherplatz Men siehe 3 2 Korrigieren Sie mit den oder Tasten siehe 3 2 ggf nur notwendig wenn auf oder ab einer bestimmten S...

Page 7: ...e anderen Aktionen im Speicherplatz Men mehr durchgef hrt werden sollen siehe 3 2 zur Grundstellung zur ckkehren indem die P Taste f r ca eine Sekunde gedr ckt wird 3 2 3 Abmelden eines nicht vorliege...

Page 8: ...lieferzustand d 3 5 Sek d 4 10 Sek d 5 20 Sek d 6 30 Sek d 7 45 Sek d 8 60 Sek d 9 90 Sek Die P Taste f r ca eine Sekunde dr cken die angezeigte Impulsdauer wird ge speichert und zur Grundstellung zur...

Page 9: ...ellererkl rung Hersteller H rmann Verkaufsgesellschaft KG Upheider Weg 94 98 D 33803 Steinhagen Produkt Transpondertaster Ger tetyp TER 1 Das oben bezeichnete Produkt entspricht aufgrund seiner Konzip...

Page 10: ...tened to 0 5 m or extended to 30 m This connection carries a safe low voltage only and is sabotage proof i e if this cable or the reader are tampered with unintentional switching actions of the decode...

Page 11: ...the connection 2 2 Connection for a potential free relay output e g for driving a door operator The decoder can also be supplied with a voltage of 24V AC DC one possibility being directly from a door...

Page 12: ...urthermore the memory location of a registered transponder key can be identified with this Note It is absolutely essential to note for which person and under which memory location a particular transpo...

Page 13: ...ny other memory location in the decoder the number of the memory location under which the transponder key has just been registered appears as a static display Enter the name of the person for which th...

Page 14: ...the memory location menu see 3 2 return to the home position by pressing button P for approx one second 3 3 Summary of the memory location menu Display of any memory Transponder key in Action that is...

Page 15: ...lows Press the and buttons simultaneously for at least one second CA clear all flashes up in the display to query whether everything should indeed be restored reset If everything is indeed to be resto...

Page 16: ...h the relevant basic safety and health requirements of the Directives stated below Any modification made to the product without our express permission and approval shall render this declaration null a...

Page 17: ...s Il est possible d activer jusqu 100 cl s r pondeuses sur un valuateur Le lecteur et l valuateur sont reli s par un c ble deux conducteurs le c ble fourni est de 5 m tres qui peut tre raccourci jusqu...

Page 18: ...s 12 V En g n ral il correspond 2 A Veuillez cependant prendre en compte les instructions accompagnant chaque g che lectrique En cas de doute s lectionnez la valeur de courant directement sup rieure 1...

Page 19: ...moire num rot es de 00 99 sont disponibles dans l valuateur Une cl r pondeuse peut tre connect e sur chacun de ces emplacements de m moire Au moyen des deux affichages sept segments et des trois touc...

Page 20: ...e fonctionnement normal lorsqu il s coule plus de 90 secondes entre deux manipulations d une touche ou deux signaux de r ponse 3 2 1 Activation d une cl r pondeuse sur le prochain emplacement de m moi...

Page 21: ...oire est libre ou effac Corrigez la liste des personnes et des num ros d emplacement de m moire en cons quence Proc dez de la m me mani re pour d sactiver ventuellement d autres cl s r pondeuses activ...

Page 22: ...non L emplacement de m moire occup activ e peut tre effac le num ro concern clignote ensuite 3 4 R glage de la dur e d impulsion Vous pouvez r gler la dur e d impulsion comme indiqu ci dessous en par...

Page 23: ...seconde CA appara t maintenant sans clignoter pour signaliser que tout doit tre remis z ro Appuyez sur une touche quelconque pour revenir en mode de fonctionnement normal Si vous ne voulez pas remettr...

Page 24: ...ispositions essentielles Directives CE Influences lectromagn tiques EN 50081 1 03 93 EN 50082 1 11 97 EN 61000 6 2 03 00 Directives de basse tension CE 98 37 EG Steinhagen 08 01 2001 Axel Becker La Di...

Page 25: ...ositivo di lettura e una chiave transponder In un decodificatore possono essere registrate fino a 100 chiavi Il dispositivo di lettura ed il decodificatore vengono collegati tra loro tramite un cavo a...

Page 26: ...riporta a partire da una tensione minima di 12 V Normalmente il carico massimo di 2 A osservare in ogni caso le indicazioni dell apriporta corrispondente In caso di dubbio selezionare per il trasforma...

Page 27: ...Nel decodificatore sono disponibili 100 locazioni di memoria in ordine numerico da 00 99 su ciascuna delle quali possibile registrare una chiave transponder Con l aiuto dei due display a sette segmen...

Page 28: ...dei tasti e v 3 2 la preimpostazione della prossima locazione di memoria che risulta libera necessario soltanto se si desidera scegliere un determinato numero di locazioni di memoria o partire da un...

Page 29: ...un secondo circa 3 2 3 Cancellazione di una chiave transponder non presente Passare se necessario al menu delle locazioni di memoria v 3 2 Impostare con i tasti o v 3 2 il numero acceso con luce fissa...

Page 30: ...orna il 9 ecc Display Durata impulso d 0 0 5 s d 1 1 s d 2 2 s impostazione originaria d 3 5 s d 4 10 s d 5 20 s d 6 30 s d 7 45 s d 8 60 s d 9 90 s Premere il tasto P per un secondo circa viene memor...

Page 31: ...zioni pagina 32 34 N Nome Annotazioni 00 5 Dichiarazione di conformit CE Produttore Verkaufsgesellschaft KG Upheider Weg 94 98 D 33803 Steinhagen Prodotto Pulsante transponder Modello TER 1 Il prodott...

Page 32: ...32 02 2008 TR30A058 RE 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43...

Page 33: ...02 2008 TR30A058 RE 33 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87...

Page 34: ...34 02 2008 TR30A058 RE 88 89 90 91 92 93 94 95 96 97 98 99...

Page 35: ...02 2008 TR30A058 RE 35 1 6...

Page 36: ...36 02 2008 TR30A058 RE 2 P P 6...

Page 37: ...02 2008 TR30A058 RE 37 3 P P...

Page 38: ...38 02 2008 TR30A058 RE 4b 4a J1 J2 J3 12 V 24 V 12 V min 2 A 230 V AC BN BK BL 6 5 8 1 2 3 J1 J2 J3 12 V 24 V 24 V AC DC 6 5 8 2 1 2 2...

Page 39: ...02 2008 TR30A058 RE 39...

Page 40: ...02 2008 TR30A058 RE...

Reviews: