Verkada AC62 is capable of supporting Verkada Readers over RS-485 and standard Wiegand readers.
The following diagram shows the wire types that are recommended for use with the Verkada AC62.
We recommend using one twisted pair for GND and VIN (power) and one twisted pair for the data (D0/D1
or A/B).
Wiring methods shall be in accordance with National Electrical Code, ANSI/NFPA 70.
Required Network Settings
An Ethernet connection with DHCP must be used to connect the AC62 to the Local Area Network
(LAN). You also need to configure firewall settings to communicate with the AC62.
●
TCP port 443
●
UDP port 123 (NTP time synchronization)
Verkada Inc. 405 E 4th Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © 2022 Verkada Inc. All rights reserved.
14
Signal
AWG
Twisted
Pair
Conductor
Shielded
Max Length
Reader Option 1 (22 AWG)
22
Yes
Yes
250 ft
Reader Option 2 (20 AWG)
20
Yes
Yes
300 ft
Reader Option 3 (18 AWG)
18
Yes
Yes
500 ft
Power (22 Gauge)
22
Yes
Yes
600 ft
Power (18 Gauge)
18
Yes
Yes
1500 ft
Request-to-Exit
22/18
Yes
Yes
1500 ft
Door Contact
22
Yes
Yes
1500 ft
You must use shield wiring with the AC62, particularly for the card reader:
●
Connect the drain wire (bare metal) from the reader cable bundle to the drain wire in the shielded
cabling. Then, connect the drain wire at the other end of the shielded cabling to Earth ground.
●
Improper grounding and shielding may result in unintended product behavior.
Shield Wiring and Grounding
Installation
Recommended Wiring