Z207937-0E
Page 5 of 8
©2021 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 0421
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
TW2 Series Installation Guide
Installation (cont.)
Switch
Function
Description
6
Setpoint output temperature range
Temperature setpoint (must be enabled on DIP switch 5)
ON - Temp range 1, 50 to 95 °F (10 to 35 °C) enabled
OFF - Temp range 2, 32 to 122 °F (0 to 50 °C) enabled
7
Display times out and turns off after
6-10 seconds of touchscreen/button
press
ON - Display Timeout enabled
OFF - Display Timeout disabled
8
Touchscreen touch functions and
buttons are disabled
ON - Touchscreen touch/button functions disabled
OFF - Touchscreen touch/button functions enabled
* Only used with voltage output mode enabled. Not applicable to setpoint output. Setpoint is 0-10V fixed.
5. With sensor base fully installed, align top of cover to mounting tabs on top of sensor base. Swing cover downward until it
latches at the bottom.
6. Install locking screw to secure cover in closed position.
Main Screen
The touchscreen user interface displays temperature sensor output values, setpoint value and menu button.
Setpoint value (temperature setpoint shown)
Fahrenheit/Celsius
Temperature value
Menu button
Menu Screen
The menu screen opens when pressing the Menu button on the main screen. Integrator’s submenu, occupancy/override,
Fahrenheit/Celsius, settings and setpoint submenu (temp or fan, determined by DIP switch settings) are displayed on the menu
screen.
Temperature setpoint
DIP switch selected
Fan speed setpoint
DIP switch selected
Touchscreen Operation