•  Sensors may be located up to 1000' away from Remote
Status Panel

•  You can use ordinary 22 gauge, unshielded wire (twisted is
preferred).

•  The 5800/5900 series sensors are safe...if unshorted on  a
powered conductor they'll only develop 24V (still, it's a good
idea to short them if not connected to panel for extended
periods of time)

• You must observe polarity of the sensors...if reversed, you
won't get an output from the panel at any set-point
adjustment...simply flip the wires.  Nothing is damaged.

•  Power LED is on when unit is powered

•  Set-point adjustment determines at what current level
monitored the Remote Panel output will trip.  Turn clockwise
to increase.

•  Status LEDs are lit when the output is energized (closed) and
the monitored current is above threshold.

REMOTE STATUS PANEL INSTALLATION

1. Mount the 5002 at your control panel (or other convenient
location).

2.  Wire the 5800/5900 sensors as shown below to the Remote
Status Panel.  Observe Polarity.

3.  Connect dry-contact reed outputs per point to your auto-
mation control panel.

4.  Power the 5002 with 24 VAC/DC from your control panel
power supply or other source.

CALIBRATION

INSTALLATION QUICK-FACTS

For undercurrent application (i.e., to detect belt loss on fan):

1. Turn on the load source and allow the motor or other load
to reach normal operating condition.

2.  For each point:  If the status LED is lit, turn the setpoint
screw clockwise until the LED goes out, then stop.  If the status
LED is  not lit, turn the setpoint screw counterclockwise  until
the LED lights, then clockwise until the LED goes out, then
stop.   Sensor threshold is now balanced at the  current level
being monitored.

3. For undercurrent indication (for most status applica-
tions), turn the setpoint counterclockwise 1/4 turn from the
position determined in step 2.  The status LED should be ON.
For variable frequency drives operating above 25 Hz, operate
drive to lowest speed operated above 25 Hz, and adjust as
sbove.  For drives operating below 25Hz or used with motors
under 5A, consult factory for set-up.   The sensor is now
calibrated to provide indication of current flows below normal
FLA.

An "open "condition of the sensor output after this adjustment
indicates that the equipment has been turned off or has failed
(belt loss, electrical failure, etc..)

NOTE:

  To calibrate the sensor for over-current indication, turn

the setpoint screw 1/4 turn clockwise rather than counterclock-
wise. If the current exceeds the setpoint, the contact will close.

NOTE:  A Status LED is lit when output is ON (Closed)  Sensor
output is closed when sensed current is above set-point.  Turn
clockwise to increase set-point.

+

+

Sense 2

Sense 1

Set Point 1

Set Point 2

Out 2

Out 1

+

+

Status LEDs

24 VAC/DC in

24VAC/DC POWER

SUPPLY

Power LED

5002 REMOTE STATUS PANEL

Automation Panel

Digital Inputs

Power In

Use Veris

5800 & 5900

Series Sensors

only