INSTALLATION GUIDE

TROUBLESHOOTING

Problem

Solution

No display

· Check external fuses.
· Verify that the display cable has not been disconnected during installation.
· Verify voltage leads are properly connected.

Reported power too low

· Verify CTs and terminals are color-matched.
· Check for phase loss.
· Check external fuses.

Reported power innaccurate

Verify meter and CTs have matching serial numbers (serial number matching does not 

apply if using 100 A CTs).

Accuracy not as specified

· Verify CTs and terminals are color-matched.
· Verify that no stray conductive materials (wire clippings, etc.) have shorted between 

the terminals.

No Pulse output (H8163 and H8167)

· Verify power is supplied in the range of 5-24 VAC/DC, with a max. load of 100 mA.
· The pulse output internal is 200 msec; verify the controller accepts this signal as input.

Pulse output wrong, display OK (H8163  

and H8167)

Set the pulse rate switch and the controller to match kWh/pulse.

No Phase Loss output (H8163  and 

H8167)

Verify power is supplied in the range of 5-24 VAC/DC, with a max. load of 100 mA.

“bAd” appears in the display (H8163  

and H8167)

Verify that the Pulse Rate slide switch is set to a valid value. 0.1 is not valid for 1600 A 

systems; 0.1 and 0.25 are not valid for 2400 A systems.

Accuracy not as specified

Verify current transformers and terminals are color-matched.

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for H81xx

Page 1: ...e to follow these instructions will result in death or serious injury A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment and...

Page 2: ...CTs only PRODUCT OVERVIEW The H81xx Series energy meter combines industrial grade split core current transformers and precision microprocessor based metering electronics It can detect phase reversal...

Page 3: ...29mm E 8 1 207mm F 5 9 150mm MINI 200Amp MICRO 100Amp MEDIUM 400 800Amp A 3 8 95mm B 1 5 38mm C 1 3 32mm D 1 1 29mm E 4 2 107mm F 4 8 121mm SMALL 300Amp LARGE 800 1600 2400Amp F E D C B A A 1 6 40 mm...

Page 4: ...ontrol data acquisition systems H8163 and H8167 6 Phaselossoutputalarm Alarm trips to protect equipment if phase voltage drops 25 H8163 and H8167 7 Pulserateselectionswitch Set the pulse output at 0 1...

Page 5: ...quire a mounting bracket For maximum accuracy run the conductor through the center of the current transformer window 4 Optionalstep perNECandlocalregulations Attach external fuses not included with th...

Page 6: ...T leads to the input terminals e g red labeled lead to red terminal Polarity is indicated in the wiring diagrams but the meter is not polarity sensitive See the Wiring section 6 Use color coding to co...

Page 7: ...phase The displayed message indicates the problem phase Amps Over The measured current is greater than 110 of the transformer range The display message indicates the problem phase Volts Over Volts A C...

Page 8: ...ween the terminals No Pulse output H8163 and H8167 Verify power is supplied in the range of 5 24VAC DC with a max load of 100 mA The pulse output internal is 200 msec verify the controller accepts thi...

Reviews: