2
➊
Accepts 1.0 V output CTs only!
Size CT appropriately for you applications
CT rating must be greater than maximum current monitored.
Orient CT arrow towards load
Observe polarity (color coding) of wiring for CTs
To interface with 5A output CTs, consult factory.
➋
Mandatory Fuse or breaker per NEC.
Max. current draw is 50 mA. Installer must ensure
compliance with local and national codes (fuse rating
100 KAIC max.)
➌
Line Voltage Selector.
Set to match line voltage
➍
Undervoltage/phase Set-point.
Phase loss output opens on alarm when below set
percentage.
➎
KWH Consumption Pulse Rate Selection
Sets maximum pulses per second at full scale operation.
Set for desired rate compatible with your automation
system.
➏
Optional KW/KWH displays.
See OPTIONAL DISPLAYS section.
➐
KW Demand Analog 4-20 mA Output
Provides instaneous KW demand analog output for input
to automtion system.
Requires external 12- 24 VDC supply.
➑
Install Resistor for KW Voltage Output
For automation systems requiring a voltage, rather than
current, KW analog output, install appropriately sized
resistor as shown.
GENERAL WIRING DIAGRAM
• This unit accepts 1.0V full-scale output Current
Transformers (CTs) only.
• Do not use 0-5A OUTPUT Current Transformers
(e.g., 200:5 type CTs) without H-6902B Adapter.
Consult Factory
• Enclose unit by bolt and nut or use a padlock to
secure.
1
2
3
5
6
7
8
4
!
IMPORTANT INSTALLATION NOTE
NOTE: The use of potential transformers
has not been evaluated by UL
LINE VOLTAGE
600
480
240/208
120
85
90
95%
80
75
UNDERVOLTAGE SET
% of full voltage
(For 208V, add 10%
to scale, i.e. 85 = 95%)
PHASE
Loss/Reversal
On-Normal
MAX. PULSE/SEC.
kWH
PULSE (N.O.)
kW
4-20 mA
PHASE LOSS
N.C.
WHT
BLK
0
A
WHT
BLK
ØB
WHT
BLK
ØC
H-6000 SERIES
kW/kWH TRANSDUCER
0.3
0.6
4.6
TEST
1.2 2.3
Orient CT arrow
towards load
Observe polarity
(color coding) of
wiring for CTs
LINE
0
B
0
C
5892
16
kW (mA)
kWH
+
-
-
+
kWH Pulse
Output
DC Supply
Voltage
ØA
Under Voltage/Phase Loss
(Opens on alarm)
LOAD
1-800-354-8556
VERIS INDUSTRIES, INC.
For use with single or three phase AC circuits only, 120 to
600 VAC, 50–60 Hz. For single phase operation, connect L-1
and L-2 only. Maximum current consumption 50 mA.
®
ØB
L-2
ØC
L-3
ØA
L-1
C
®
®
NRTL/C
Optional Potential
Transformers for
voltages above 600 V
Optional Surge
Suppressor
FUSE
FUSE
FUSE
FUSES: 600 V 1/4 AMP, 100 KAIC
L-1
L-2
L-3
NOTE:
Consult factory for
single phase installation
2
3
4
5
6
7
1