background image

Z207933-0A 

Page 1 of 5 

©2021 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0321 

 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  Read and understand the instructions before installing this product.

•  Turn off all power supplying equipment before working on it.

•  The installer is responsible for conformance to all applicable codes.

If this product is used in a manner not specified by the manufacturer, the protection 

provided by the product may be impaired. No responsibility is assumed by the 

manufacturer for any consequences arising out of the use of this material.

Installation Guide

Air Quality

Product Identification

Product Overview

The CWE2 Series of air quality sensors for living space are for use with BAS controllers designed to accept  
4 to 20mA, 0 to 5 Vdc or 0 to 10 Vdc outputs. These sensors measure CO2 levels using a dual-beam, non-dispersive 
infrared (NDIR) technology. 

The CWE2 Series Economy sensor has an accuracy of ±30 ppm ±3% of measured value, features 2-wire 4 to 20mA 
and 3-wire voltage outputs, and is available with optional temperature output. 

CWE2 Series

Economy Wall Mounted Air Quality Sensors

Specifications

OPERATING ENVIRONMENT

Input Power

Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz

Max. Current

20 mA

Analog Output

Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V

Operating Temp. Range

0 to 50 °C (32 to 122 °F)

Operating Humidity Range

0 to 95% RH non-condensing

Housing Material

High-impact ABS plastic

Terminal Block Torque

0.5 to 0.6 N-m (0.37 to 0.44 in-lbf)

CO2 TRANSMITTER

Sensor Type

Dual-beam, non-dispersive infrared (NDIR), diffusion sampling

Output Range

0 to 2000 ppm

Accuracy

±30 ppm ±3% of measured value

Repeatability

±20 ppm ±1% of measured value

Startup Time

≤20 seconds

Response Time

≤ 75 seconds for 90 degree step change

Max. Load Resistance*

100 Ω at 20 Vdc 
250 Ω at 24 Vdc 
500 Ω at 30 Vdc

WIRING TERMINALS

Terminal Blocks

Screw terminals, 18-24 AWG

Screw Terminal Torque

0.2 N-m (2.0 in-lbF) max.

CWE2

CWE2

User Interface

Blank

C

D
H

K

M

N

= None
= 1000 PT RTD
= 10K T2 thermistor
= 10K T3 thermistor
= 10K curve G/11K shunt
= 20K NTC thermistor
= 1.8K TAC thermistor