-8-
Z202833-0K
©2006 Veris Industries
10061
SPECIFICATIONS
General
Operating Temp. Range .........................................0 to 60ºC (<95%RH, non-condensing)
Storage Temp. Range .............................................-40ºC to 70ºC
Power Source .........................................................120 VAC (+10/-25%), line-to-neutral, 50/60 Hz. (240VAC for H663SM-
xxE
)
Measured Current Inputs
Number of Channels ...............................................42
Frequency ..............................................................50/60 Hz.
Sample Frequency .................................................1280 Hz.
Update Rate ...........................................................1.2 sec
Accuracy .................................................................±5% from 5A to 50A
10A to 100A (H663SM-42H only)
Connection to Conductor .......................................Inductive split-core CT
Network Communications
Type ........................................................................Modbus RTU
Connection .............................................................DIP switch-selectable 2-wire or 4-wire
Address ..................................................................DIP switch-selectable address 1 to 247
Baud Rate ...............................................................DIP switch-selectable 2400, 4800, 9600, 19200
Parity .....................................................................DIP switch-selectable NONE, ODD, EVEN
Communication Format .........................................8-data-bits, 1-start-bit, 1-stop-bit
Termination ...........................................................5-position depluggable connector
Defaults
Warning Register ...................................................60% of current sensor max. (configurable)
Alarm Register .......................................................70% of current sensor max. (configurable)
Breaker Size Register ..............................................20A
Dimensions
Circuit Board(L x W) .................................................7.25” x 5.75”
Split-Core CT’s (6’ leads) ...........................................1.04" x 1.04" x 1.58"
Lithium Battery Life .................................................5 years (Replace with type CRF 1220 or equiv.)
CAUTION! DANGER OF EXPLOSION IF BATTERY IS INCORRECTLY REPLACED. REPLACE
ONLY WITH THE SAME OR EQUIVALENT TYPE RECOMMENDED BY THE MANUFACTURER. DISPOSE OF
USED BATTERIES ACCORDING TO THE MANUFACTURER'S INSTRUCTIONS.
Measured Currents .............................. Current Range 0-50A or 0-100A (H663SM-42H)
Primary Fusing .................................... 250VAC/100mA, 5x20mm, (if equipped)Littlefuse 218 series or equivalent
Safety
UL Listed under standard 508 as an “open type device”.
Critical components evaluated to UL 1950
U.S. Patent Number 6,330,516