Z207135-0C
Page 9 of 10
©2016 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 0916
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
TM
Installation Guide
Air Quality
Conformance Statement
BACnet Protocol Implementation Conformance Statement
Vendor Name: Veris Industries
Product Name: Veris GWNP Gas Platform Base
Product Model Number: GWNPxx
Application Software Version: 1.0
Firmware Revision: 0.8.2
BACnet Protocol Version: 1
BACnet Protocol Revision: 12
Product Description: Environmental Sensor
BACnet Standardized Device Profile (Annex L):
BACnet Application Specific Controller (B-ASC)
List all BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-B,DS-RPM-B,DS_WP-B, DS-COV-B,DM-DDB-B,DM-DOB-B,DM-DCC-B
Segmentation Capability: Segmentation not supported
Standard Object Types Supported:
No dynamic creation or deletion supported
No proprietary properties or object types
(other information about objects on preceding pages)
Data Link Layer Options: MS/TP master (Clause 9), baud rates: 9600, 19200, 38400, 76800
Device Address Binding: Static device binding is not supported. (No client functionality is included).
Networking Options: None
Character Sets Supported: ANSI X3.4
Summary of Contents for GWNP Series