NOTE: This product is factory calibrated. The typical CO
2
sensor calibration interval
is 5 years, depending on specific site installation factors. As of the date of this
document, compliance with ANSI/ASHRAE 62-2001 requires minimum on-site
accuracy verification intervals of 6 months or per the building operation and
maintenance manual. Accuracy verification should be performed using either a
comparison to a known reference or the CO
2
gas calibration kit available from Veris
Industries as model AA01.
WARNING: CO
2
sensor calibration requires a gas calibration kit. Performing calibration
without a gas kit will cause erroneous readings. Consult factory for calibration kit.
Select 0 ppm Cal Gas option.
4.
Continue flowing gas through the sensor. Estimated calibration time is 5 minutes.
5.
Unit returns to run mode when calibration is complete.
CWL
CDL
for cdl/cwl devIce wIth Pear-
ShaPed SenSor
Remove cover to the device.
1.
Connect hose to plastic port located on sensing module and flow gas (Nitrogen) O
2.
ppm CO
2
gas through the sensor.
Connect hose here
CWL
CDL
NITROGEN
GAS
Regulator
Valve
Push and hold plus and minus buttons for 5 seconds to enter Calibration mode. At
3.
each menu option, use the arrow to change values. Push enter for next option.
E
X X
R
X
X
X X X X
S
A L
I
X
X X
X
X
X X
X
Displays serial number
Displays model number
Range is -5 to 5
°
C ,
0.1
°
C increment
Range is -10 to 10%,
0.1% increment
Options are Yes/No
Options are None, 0, 400
Unit will automatically return to run
mode when calibration is complete.
CWL ONLY