VERIS INDUSTRIES, INC. GWN Series Installation Manual Download Page 2

Z206728-0A 

Page 2 of 3 

©2014 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 05143 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Air Quality

GWN Series

TM

Product Diagram

Relay Setpoint Selection Switch
(see the applicable AGxx sensor 
installation guide for setpoint 
information)

Pin Connector for AGxx gas sensor

An AGxx sensor is required for GWN 

operation. Sensors are sold separately.

Voltage Output 

Selection Switch

(Not present on mA/relay 

or relay only models)

OUTPUT

5V     10V

SETPOINT

LO     HI

LED Indicators

left - red
center - yellow
right - green

The voltage output selection switch is only available on voltage output models. For mA/relay output and relay only models, this 
space is empty.

Use the relay setpoint selection switch to select either the high or low levels of the low setpoint. These values vary among the 
available AGxx sensors. See the applicable AGxx sensor installation guide for more information about relay setpoint options. 

The LED indicators allow determination of device status at a glance. The GWN includes a light blocking insert that can be set in 
place of the light pipes if this visibility is not desired.

LED Blink Codes

LED

Description

Yellow

•  Off during normal conditions.
•  On solid when the low setpoint is reached.
•  1 flash every 10 seconds if possible sensor damage is detected.
•  2 flashes every 10 seconds if the sensor requires replacement.
•  4 or more flashes every 10 seconds if internal problems are detected, such as if the unit needs servicing or if the operating 

temperature is out of range.

Green

•  On solid during normal operation.

Red

•  Off during normal conditions.
•  On solid when the high setpoint is reached.
•  Flashes continuously when the sensor reading is over range.

All LEDs

•  Flash once when the device is initially powered.
•  Flash while the platform is auto-resetting, such as when a sensor is installed.