Figure 18: NS sensors with terminals addressable
Table 13: NS sensors with terminals addressable
1
Thermostat circuit board
Note:
Jack J2 is for commissioning tools.
2
Address switch
3
Terminal block on the NS sensor. Connector on the mounting base slides into W4
pins on the circuit board
4
To next device on the sensor bus if required
5
From previous device the on the sensor bus
Table 14: NS sensor addresses
DIP switch settings
Available DIP switch
addresses
Switch 4
Switch 2
Switch 1
199
Off
Off
Off
200
Off
Off
On
201
Off
On
Off
202
Off
On
On
203
On
Off
Off
Note:
Addresses 204 to 206 are not supported.
Setup and adjustments
Setting the ZEC510 device address
Before you apply power or operate the ZEC510, you must set a valid and unique device address for
the controller on the bus. Ensure that your system meets the following prerequisite configuration
and complete the addressing steps.
Prerequisites
• Identify the addresses when you design the system before the installation so that the rest of
the devices on the bus do not conflict with the address you select for the ZEC510.
Verasys ZEC510 VAV Controllers Installation Guide
26