Table 4: Supported VAV controllers

Feature

Staged

Incremental

Proportional SCR

Up to five CO

2

 sensors (high select)

Yes

Yes

Yes

Staged supplemental heat

Yes

No

No

Incremental supplemental heat

No

Yes

Yes

Table 5: Supported COBP controller

Feature

LC-ZEC310-0

Modulated box heat

Yes

On/Off box heat

Yes

Modulated supplemental heat

Yes

PWM supplement heat (10 sec duty cycle)

Yes

On/Off supplemental heat

Yes

Occupancy sensing input

Yes

Up to five net sensors (averaging)

Yes

Up to five CO

2

 sensors (high select)

Yes

Extra output for second damper actuator

Yes

Note: 

Box heat is any heat source that is located in the duct. Supplement heat is any heat

source that is located outside the duct.

Ordering information

Contact your Johnson Controls representative to order Verasys system or related products. See the

following table for product code numbers and product descriptions.

Table 6: Ordering information

Product code

number

Description

LC-SBH200-0

SBH with Wi-Fi adapter

LC-SBH200-0S

SBH with Wi-Fi adapter and power supply

LC-SBH200-0LA

SBH for Latin America

LC-VZC100-0

Verasys Zone Coordinator for VAV and COBP applications

LC-VZCPNL-0

Verasys Zone Coordinator for VAV and COBP applications - panel version

LC-VEC100-0

Verasys Equipment Controller for third-party RTU (VAV, COBP), with staged heating and staged cooling

application. Other applications are available. For application files and documentation, visit 

http://

verasyscontrols.com

.

LC-ZEC510-0

Configurable VAV Box Controller, all fan types, staged, incremental and proportional SCR heating

Note: 

You can order the ZEC510 controllers mounted and wired in VAV box assembly. For more

information, contact your Johnson Controls representative.

LC-ZEC310-0

Field-installed zone controller, no damper

Note: 

You can order the LC-ZEC310-0 controller mounted on round dampers. For more

information, refer to the 

Zone and Bypass Damper Controllers Catalog Page (LIT-1901009)

.

LC-BYP200-0

Field-installed Bypass Damper Controller, no damper

Note: 

You can order the LC-BYP200-0 controller mounted on round dampers. For more

information, refer to the 

Zone and Bypass Damper Controllers Catalog Page (LIT-1901009)

.

LC-VAC1000-0

18 point 24 VAC Application Controller with no application loaded. For application files and

documentation, visit 

http://verasyscontrols.com

.

LC-VAC1001-0

18 point 24 VAC Application Controller with lighting controller application loaded

LC-VAC1002-0

18 point 24 VAC Application Controller with input and output controller application loaded

LC-VAC1100-0

18 point 240 VAC Application Controller with no application loaded. For application information,

contact Verasys support.

LC-VAC3000-0

32 point 24 VAC Application Controller with no application loaded. For application files and

documentation, visit 

http://verasyscontrols.com

.

Verasys System Product Bulletin

16

Summary of Contents for LC-BYP200-0

Page 1: ...C ZEC510 0 LC ZEC310 0 LC BYP200 0 LC VAC1000 0 LC VAC1001 0 LC VAC1002 0 LC VAC1100 0 LC VAC3000 0 LC IOM3711 0 Building Technologies Solutions www johnsoncontrols com 2021 04 08 Verasys System Produ...

Page 2: ...2 Verasys System Product Bulletin...

Page 3: ...features 12 Constant Volume application 12 Sideloop application 12 Verasys Zone Coordinator 12 TEC30xx or TEC36xx Thermostat controllers 12 Verasys Pro Wireless Field Bus System 13 Ideal applications...

Page 4: ...4 Verasys System Product Bulletin...

Page 5: ...sensors and damper assemblies All devices self configure and the Verasys Smart Building Hub SBH monitors the devices Through the SBH you can access the system using either a laptop smart phone or tab...

Page 6: ...ctivity Verasys Enterprise is a cloud based solution that provides a multi site aggregation of equipment data alarms setpoints and schedules to authorized users The enterprise application provides a h...

Page 7: ...users Verasys Tenant User Guide LIT 12013613 Using the SBH to configure the Verasys system Verasys System User s Guide LIT 12012371 Overview of Verasys system components features and operating modes...

Page 8: ...72 Verasys Input Output Module IOM Installation Guide Part No 24 10143 1256 Verasys ZEC510 VAV Controllers Installation Guide Part No 24 10143 01485 Verasys 18 Point 240 VAC Application Controller Ins...

Page 9: ...ume Controller Application Note LIT 12013067 Verasys Input Output Module Application Note LC VAC1002 0 LIT 12012992 Verasys Lighting Controller Application Note LIT 12012524 Verasys Sideloop Controlle...

Page 10: ...zone or bypass damper assembly when they are shipped The Zone and Bypass Damper controllers include advanced operating modes and multiple features that ensure occupant comfort A carbon dioxide CO2 dem...

Page 11: ...ghting controller VAC1001 The Verasys Lighting controller VAC1001 is a Verasys Application controller that controls up to nine lighting contactors that are grouped in zones You can control and schedul...

Page 12: ...rol a mixed air damper or set a minimum outside air damper position and meet Title 24 compliance for the state of California Other supported features include occupancy scheduling outdoor air lockouts...

Page 13: ...ficult or aesthetically unappealing to hardwire between products Examples of these locations include the following Office buildings university campuses educational facilities and other commercial stru...

Page 14: ...ntroller to the system bus its data automatically fills a predefined set of views based on the object type You can create profiles for third party controllers Profiles provide the following benefits Y...

Page 15: ...mizer Yes Yes Yes Yes Title 24 economizer Note 24 sequence and alarm notification is implemented from within the application State of California certification is pending Yes No Yes Yes Demand ventilat...

Page 16: ...ed cooling application Other applications are available For application files and documentation visit http verasyscontrols com LC ZEC510 0 Configurable VAV Box Controller all fan types staged incremen...

Page 17: ...SBH Manufacturer Model Name D LINK DWA 131 E D LINK DWA 171 A D LINK DWA 171 C NETGEAR A6100 TP LINK Archer PREMIERTEK PT 8811AU Table 9 Zone controller accessories Product code number Description Zo...

Page 18: ...fan coil and zoning No Yes Yes White TEC3012 16 000 On off or floating fan coil and zoning No Yes No White TEC3013 14 000 On off or floating fan coil and zoning Yes Yes Yes White TEC3022 13 000 0 to...

Page 19: ...Yes White TEC3622 16 000 0 to 10 VDC proportional fan coil and zoning No Yes No White TEC3623 14 000 0 to 10 VDC proportional fan coil and zoning Yes Yes Yes White TEC3630 13 000 Single or two stage...

Page 20: ...ZFR1821 Note Use the ZFR1821 EMT mount repeater for above the ceiling mounting Use the alternative ZFR1822 Pro Router for flush wall mount or below the ceiling mount applications Use a field provided...

Page 21: ...Two SA FC ports RJ12 6 pin port connects with 1 5 m 4 9 ft RJ 12 field bus cable and one screw terminal plug 4 pin Three USB ports one Micro B port and two USB A ports All support USB 2 0 and Open Hos...

Page 22: ...C in 0 5 increments Heating control 40 0 F 4 5 C to 90 0 F 32 0 C Temperature range Cooling control 54 0 F 12 0 C to 100 0 F 38 0 C Temperature 0 9F 0 5C at 70 0 F 21 0 C typical calibrated Accuracy H...

Page 23: ...1 2 in Square shaft size 10 mm 3 8 in Serrated actuator coupling for additional grip Dimensions H x W x D 165 mm x 125 mm x 73 mm 6 5 in x 4 92 in x 2 9 in Differential pressure transducer BYP200 onl...

Page 24: ...vice addresses 1 to 255 Communications bus BACnet MS TP 3 wire zone bus between the supervisory controller and the field controller 3 wire sensor bus between the controller network sensors and other s...

Page 25: ...ly mounted control suitable for DIN rain mounting Intended to mount in remote panel Type 1 C Micro interruption 330 V rated impulse voltage 125 C ball pressure test Australia and New Zealand RCM Mark...

Page 26: ...ic three available modes see application note for wiring diagrams and usage Voltage input 0 VDC to 10 VDC Current sense input 4 mA to 20 mA Resistive inputs dry contact inputs Four binary inputs Defin...

Page 27: ...ly Class 1 North America SELV Europe Power consumption 20 VA maximum for LC VAC110x 0 Note VA rating does not include any power supplied to the peripheral devices connected to BOs or COs This can cons...

Page 28: ...put output Fixed spade terminals Sensor system and modbus 4 wire and 3 wire pluggable screw terminal blocks Sensor Bus tool port RJ 12 6 pin modular jack Mounting Horizontal on a single 35 mm DIN rail...

Page 29: ...ble modes see application note for wiring diagrams and usage Voltage input 0 VDC to 10 VDC Current sense input 4 mA to 20 mA Resistive inputs and dry contact inputs 12 Binary Inputs Defined as dry con...

Page 30: ...60 Hz class 2 Transformer allowance 2 5 VA maximum 2 VA typical Provided through the three position 24 V screw terminal pluggable block 15 VDC 180 mA 7 VDC to 18 VDC 185 maximum current draw on the FC...

Page 31: ...less Field Bus Router wall mount for Field Controller Router Applications LC ZFR1821 0B Wireless Field Bus Router conduit mount with 24 VAC Power Supply for Field Controller Router Applications LC ZFR...

Page 32: ...n emissions compliance United States This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to p...

Page 33: ...tware terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license open source...

Page 34: ...2021 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice...

Reviews: