APPENDIX B - (EXAMPLES OF DEVICE FAULTY WORKING)
SYMPTOMS
POSSIBLE REASON
Excessive vibration or
noise
Damaged impeller
Dirt accumulated on impeller caused loss of balance;
Impeller loss of balance;
Parts rubbing;
Damage or wear of bearings;
Failed fan start-up/
stop during
operation.
Rubbing between fan impeller and housing or foreign body (e.g. tool left after installation);
Overload of motor or electronic controller;
Damage or wear of bearings;
Power failure or phase failure;
Too high or too low supply voltage;
Electronic controller lock up (power restart needed);
No power restart done after activation of motor protective modules.
Protective modules or
devices activation
during fan
work and overheating
Excessive start-up time;
Motor overload;
Shortcut in power adapter circuits of EC motor;
Too often start-ups;
Improper set of protection circuit breaker and / or incorrect set of protective relays;