Ventur MPT Assembly, Operation And Maintenance Instructions Download Page 2

Version V-6.1  © Ventur tekniska ab 2010 

 

Connection of three-phase AC unit 

 

       (high voltage Y-connection

)

  

 

          (low voltage 

-connection)

 

 
 
Connection of single-phase AC unit 

 

The arrows indicate the direction of rotation seen from the shaft side of the motor. 
 

Inspection of rotation direction 

Start up the fan for a short moment, inspect the rotation direction. The rotation direction of the impeller must be in 
accordance with the arrows on the motor. If not, move the L1 and L3 phases for three-phase operation or check the 
wiring circuit in the terminal box for single-phase operation. Incorrect rotation direction will cause reduced capacity 
of the fan and could damage the impeller. 
 

Start of operation 

If the rated current indicated on the rating plate is being exceeded during operation, it should be checked whether 
the available supply voltage and frequency are in accordance with the embossed data. The drive motor is sized for 
the power requirements up to a maximum allowed pressure (see capacity curves in catalogue). At higher pressures 
the power consumption will increase with overheating as consequence. Observe that overheating could occur 
because of compression heat even when the power of the motor is not exceeded. Installation of thermal protection 
is recommended preventing overheating. Overloading can be avoided through installation of relief valve which will 
keep the maximum allowed working point. Do not expose the fan to vibrations and shock. 
 

F Maintenance 

MPT/MPB-fans are equipped with enclosed grooved ball bearings that do not need lubrication. The grease filling is 
sufficient for the whole service life of the bearings. 
 

Attention! 

Repair work on fans should be done by the manufacturer. We do not take any responsibility for repairs done by 
third parties. 
 

Spare parts list 

When ordering spare parts, please state the size of the fan and part number in accordance with the spare parts list 
(page 5). 
 

1                        N 

 U1        Z1 

Z2        U2 

1                        N 

 U1        Z1 

Z2        U2

1           2           3 

 U1        V1        W1 

W2        U2        V2 

1           2           3 

 U1        V1        W1 

W2        U2        V2 

Version V-6.1  © Ventur tekniska ab 2010 

 

H Manufacturer 

Declaration 

 
 

EC Declaration of conformity for machinery 

(Machinery Directive 2006/42/EC, Annex 2, A) 

 
 

Manufacturer: Ventur tekniska ab 
 

 

Manufakturgatan 7 A 

 

 

SE-417 07 GÖTEBORG 

  Sweden 
 
Name and address of the person authorised to compile the relevant technical file: 
Name: Peter 

Skoow 

Address: See 

above 

 
 
Herewith declares that: 

Centrifugal Fans Type MPT/MPB 

 

  is in conformity with the relevant provisions of the Machinery Directive (2006/42/EC) 

 

  is in conformity with the provisions of the following other EC-Directives: 

 

Low Voltage Directive 2006/95/EC  

 
  
And furthermore, declares that: 
 

  the following European harmonised standards have been used: 

 

EN ISO 12100-1 

 

EN ISO 12100-2 

 
 
This EC Declaration of conformity for machinery is only valid when all conditions stated in the “Assembly-, 
Operation- and Maintenance Instructions, EC-declaration” are fulfilled. 
 
The machinery must not be put into service until the final machinery or construction into which it is to be 
incorporated has been declared in conformity with the provisions of the Machinery Directive 2006/42/EC. 
 
If modification of the unit is made without our approval, this declaration becomes invalid. 
 
 
 
Göteborg 2010-05-10 
 

 

Peter Skoow 
MD, Ventur tekniska ab 
 
 
 
 
 
 
 
 
 

Adress

 

Telefon  

 

Telefax

 

Ventur tekniska ab 

Nat    

031-23 50 80 

 

 

Nat 

 031-23 87 98 

Manufakturgatan 7 A 

Int 

+46 31 23 50 80 

 

 

Int  

+46 31 23 87 98 

SE-417 07  GÖTEBORG, Sweden 

E-mail:  

[email protected] 

 

 

Web: 

 www.ventur.se 

Reviews: