10
VUTR 280 V (E) EC
www.ventilation-system.com
HUMIDITY SENSOR MOUNTING
The HV2 humidity sensor is not included in the delivery set and can be ordered separately.
To install the humidity sensor, take off the front panel and remove the extract filter out of the unit.
Install the humidity sensor into the mounting bracket on the inner side of the unit.
Connect the cable with a connector (located inside the unit) to the sensor.
SERVICE SIDE CHANGE
1. Make sure of the correct unit service side selection. Unit mounting position should enable free excess to the service panel for
maintenance and service operations.
Supply air
Intake air
Exhaust air
Extract air
Supply air
Intake air
Exhaust air
Extract air
2. Unscrew the 6 screws and remove the mounting bracket. Attach the mounting bracket to the opposite side of the unit. Unscrew the
two screws on the side stops (located at the bottom of the unit) and attach them to the opposite side.