4. Selecting the special day setpoint.
Press the
button to select the “Set.” parameter and then use the
and
buttons to select the setpoint required on the special day.
Once done with the special day setup press the
button to save
the changes. After pressing the
button the cursor will jump to
the first step of setting the next special day.
5. Setting up other special days.
Other special days are set up similarly.
Setting up setpoints
Page 4/4
The setpoints for schedule entries are programmed on page 4/4.
Setting up setpoints.
Press the
button to select a parameter.
Then use the
and
buttons to set the desired parameter value.
You may program up to three entries. Set the fan speed and temperature for each setpoint.
UNIT PARAMETER SETUP
To set up the unit parameters enter the user parameters menu and
select “Parameters”.
The “Parameters” menu consists of four pages. To navigate between
the pages use the
and
buttons.
Page 1/04 Fan speed setting.
Use the
button to select the supply or exhaust fan speed as
necessary and then press the
and
buttons to set the speed
value as a percentage of the maximum speed.
After that press the
button to save the settings.
The “Main sensor” parameter allows changing the temperature
measuring location to account for the value and subsequent
processing by the firmware.
If the unit serves a number of spaces the parameter value should be
set to “Exh. air”
When setting or editing a parameter the th-Tune” control panel must
be installed in the space supplied by the unit.