11
www.ventilation-system.com
VUT 2000/3000 PBE EC
DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY OPERATIONS.
THE UNIT MUST BE CONNECTED TO POWER MAINS BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE
MANUFACTURER'S LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED
AND WILL VOID THE WARRANTY.
The unit is rated for connection to three-phase 3~400 V/50 Hz power mains. For electric installations use insulated durable heat-resistant
conductors (cables, wires) with the minimum wire cross section 2.5 mm
2
.
The above conductor cross section value is tentative and in practice must be based on the wire type, maximum permissible heating
temperature, insulation, length and installation method.
Connect the unit to power mains through the external automatic circuit breaker with a magnetic trip integrated into the fixed wiring
system with the rated current not below the rated current consumption.
The terminal block with the prewired control unit is located inside the control unit compartment.
To connect the power and the ground cable, route the cables through the airtight electric lead-in in the unit casing and connect these to
the terminal block. The wiring diagram for connection of the air handling unit to power supply is on the back side of the lid.
CONNECTION TO POWER MAINS
VUT 2000 PBE EC A21 EXTERNAL WIRING DIAGRAM
L2 L1 1 2 3 4 5 6 7 8 9 10
C
11
NC
12
C
13 14 15 16 17 18 19 20 21 22 23 24 25 26
NO GND 0-10 +24V Gnd A B +24V NO C NO C NO C
P1*
1
2
PK1*
CC
U*
N L3
X1
SM1*
SM2*
**U
Boost*
CO2*
1
2
Gnd 0-10V +24V Gnd
+24V
A
B
1
2
**U
1
2
P1*
1
2
PK1*
CC
U*
X1
SM1*
SM2*
**U
Boost*
CO2*
1
2
Gnd 0-10V +24V Gnd
+24V
A
B
1
2
**U
1
2
~400 V 50/60 H
z
Design
Name
Type
Wire***
Note
SМ1
*
Supply air damper actuator
NO
2 x 0.75 mm
2
3 A, 30VDC/~250 AC
SМ2
*
Extract air damper actuator
NO
2 x 0.75 mm
2
3 A, 30VDC/~250 AC
РК1
*
Contact from fire alarm panel
NC
2 x 0.75 mm
2
remove the jumper
CCU
*
Cooler control
NO
2 x 0.75 mm
2
3 A, 30VDC/~250 AC
Р1
*
External control panel
4 x 0.25 mm
2
Boost
*
Boost mode On/Off contacts
NO
2 x 0.75 mm
2
CO2
*
External CO
2
sensor
3 x 0.25 mm
2
*Is not included in the delivery set.
**The supply voltage U of the SM1, SM2 external dampers is selected depending on the type of dampers.
*** Maximum connecting cable length is 20 m!
Output parameters: terminals 21-26 – 3 A, 30VDC/~250VAC (“dry contact”).
— ELECTRIC SHOCK HAZARD!
remo
ve the
jump
er
gr
een
br
own
yello
w
whit
e
Summary of Contents for VUT 2000 PBE EC
Page 1: ...VUT 2000 PBE EC VUT 3000 PBE EC Heat recovery air handling unit USER S MANUAL ...
Page 17: ...17 www ventilation system com VUT 2000 3000 PBE EC ...
Page 18: ...18 VUT 2000 3000 PBE EC www ventilation system com ...
Page 19: ...19 www ventilation system com VUT 2000 3000 PBE EC ...
Page 20: ...V255 1EN 02 ...