5
www.ventilation-system.com
TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to
80 %.
To prevent condensation on the internal walls of the unit, it is necessary that the dew point temperature of transported air is 2-3 °C below
the surface temperature of the casing.
The unit is rated as a Class I electrical appliance. Hazardous parts access and water ingress protection rating:
• IP44 for the unit motors
• IP22 for the unit connected to the air ducts
The unit design is constantly being improved, so some models may be slightly different from those ones described in this manual.
TECHNICAL DATA
MODEL
VUT 180 P5(B)
VUE 180 P5(B)*
VUT 180 P5
VUE 180 P5*
Voltage [V/50 (60) Hz]
1~220-240
Maximum fan power [W]
87
117
Maximum unit current without a heater [A]
0.71
0.54
Maximum air flow [m
3
/h]
220
Sound pressure level at 3 m distance [dBA]
33
35
Transported air temperature [°C]
from -25 up to +60
Casing material
EPP
Insulation
EPP (30-15 mm)
Filtering class of the extract filter
G4
Filtering class of the supply filter
G4, F7
G4 (F7 – optional)
Weight [kg]
14
Heat recovery efficiency [%]
86-98
79-94
86-98
79-94
Heat exchanger type
counter-flow
Heat exchanger material
polystyrene
enthalpy
membrane
polystyrene
enthalpy
membrane
* The unit is equipped with an enthalpy heat exchanger that doesn’t require condensate drainage.
MODEL
DIMENSIONS [MM]
Ø
D
Ø
D1
A
A1
A2
B
B1
B2
B3
H
H1
VUT/VUE 180 P5(B) (EC)
150
18
1009
900
302
650
600
326
163
264
250
А
B
H
H1
А1
А2
øD1
øD
B1
B3
B2