VUE P3 A3/A4

www.ventilation-system.com

DESIGN AND OPERATING PRINCIPLE

Supply fan

Extract fan

Extract air filter

Control unit

Thermostat for heat exchanger freeze protection

Cable glands

Cross-flow heat exchanger

Supply air filter

Controller

Power cord with a plug

Inspection hatch for filter and heat

exchanger maintenance

Left-handed modification

The service side of the unit is equipped with a detachable inspection hatch on manual bolts for filter and heat exchanger cleaning and 
replacement operations. The plate enthalpy cross-flow heat exchanger is made of polymerized cellulose. 
The control unit is positioned inside the unit casing . The power cable and grounding cables are connected to the control unit via the 
cable gland located at the side of the unit. The unit is equipped with a controller and a power cord with a Euro Plug XP. 
Warm stale extract air from the room flows into the unit, where it is filtered by the extract filter, then air flows through the heat 
exchanger and is exhausted outside by the extract fan. Cold fresh air from the outside flows into the unit, where it is cleaned by the 
supply filter. Then the air flows through the heat exchanger and is directed to the room with the supply fan. 
Supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to the cold fresh air.
The air flows are fully separated while flowing through the heat exchanger. Heat recovery minimizes heat losses, which reduces the 
cost of space heating in the cold season. The enthalpy heat exchanger provides both heat and humidity recovery.  
In warm seasons the heat exchanger operates to cool down and dehumidify the supply air. In cold seasons the heat exchanger 
operates to warm up supply air and humidify it. Water vapour from the humid extract air is condensed and absorbed by the heat 
exchanger plates. The recovered humidity and heat are transferred to the supply air flow. The air streams are fully separated within the 
heat exchanger and the microbes and smells are isolated.

LEFT-HANDED AND RIGHT-HANDED MODIFICATIONS

The figure below shows the arrangement of spigots for left- and right-handed modifications. Choosing the right arrangement can 
improve the ease of installation, shorten the length of the ducts and reduce the number of air duct bends (elbows)

R

EXTRACT AIR

SUPPLY AIR

INTAKE AIR

EXHAUST AIR

INTAKE AIR

SUPPLY AIR

EXHAUST AIR

EXTRACT AIR

Left-handed modification

Right-handed modification

Summary of Contents for VUE 100 P3

Page 1: ...USER S MANUAL VUE 100 P3 VUE 200 P3 VUE 300 P3 VUE 450 P3 Heat and energy recovery air handling unit ...

Page 2: ...actical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country Safety requirements 2 Purpose 4 Delivery set 4 Designation key 4 Technical data 5 Design and operating principle 7 Mounting and set up 9 Connection to power mains 10 Technical maintenance 11 ...

Page 3: ... can damage the impeller blades While mounting the unit avoid compression of the casing Deformation of the casing may result in motor jam and excessive noise Misuse of the unit and any unauthorised modifications are not allowed Do not expose the unit to adverse atmospheric agents rain sun etc Transported air must not contain any dust or other solid impurities sticky substances or fibrous materials...

Page 4: ...d for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety Children should be supervised to ensure that they do not play with the unit Ensure that the unit is switched off from the supply mains before removi...

Page 5: ...ecovery air handling unit The unit is designed to ensure continuous mechanical air exchange in houses offices hotels cafes conference halls and other utility and public spaces as well as to recover the heat energy contained in the air extracted from the premises to warm up the filtered stream of intake air The unit is not intended for organizing ventilation in swimming pools saunas greenhouses sum...

Page 6: ...cation for example of new buildings The unit is rated as a Class I electrical appliance Hazardous parts access and water ingress protection rating IP22 for the unit connected to the air ducts IP44 for the unit motors The unit design is constantly being improved thus some models may be slightly different from those described in this manual Parameter VUE 100 P3 VUE 200 P3 VUE 300 P3 VUE 450 P3 Unit ...

Page 7: ... A B1 ØD B L L A B A B Model Dimensions mm Ø D A A1 B B1 H H1 L VUE 100 P3 100 734 600 481 571 204 223 300 VUE 200 P3 100 987 854 704 793 222 241 480 VUE 300 P3 150 987 854 704 793 227 246 480 VUE 450 P3 150 1157 1024 754 843 277 296 488 ...

Page 8: ...hen the air flows through the heat exchanger and is directed to the room with the supply fan Supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to the cold fresh air The air flows are fully separated while flowing through the heat exchanger Heat recovery minimizes heat losses which reduces the cost of space heating in the cold season The enthal...

Page 9: ...fter temperature increase the unit returns to the previous operation mode In the Defrosting mode the supply fan is turned off and the heat exchanger is warmed up with warm extract air flow To set the thermostat threshold value turn the control knob to the desired position The recommended thermostat operating temperature is 3 C factory setting EXTRACT AIR SUPPLY AIR INTAKE AIR EXHAUST AIR INTAKE AI...

Page 10: ...alist Before mounting make sure the casing does not contain any foreign objects e g foil paper The minimum distance between the unit and the ceiling should be at least 20 mm To attain the best performance of the unit and to minimise turbulence induced air pressure losses connect the straight air duct section to the spigots on both sides of the unit while mounting Minimum straight air duct length e...

Page 11: ... It is recommended to select the nominal current of the circuit breaker from the standard series following the maximum current of the connected unit The circuit breaker is not included in the delivery set and can be ordered separately Units with an A3 control panel VUE 100 VUE 200 VUE 300 VUE 450 Units with an A4 control panel VUE 100 VUE 200 VUE 300 L N PE C1 C1 C2 C2 T SL 1 2 3 L N PE T C1 C1 C2...

Page 12: ...nce a year Some dust may accumulate on the heat exchanger block even in case of regular maintenance of the filters To maintain high heat exchange efficiency periodical dry cleaning is recommended Use a vacuum cleaner with a narrow nozzle 3 Fan maintenance once a year Even in case of regular maintenance of the filters some dust may accumulate inside the fans and reduce the fan performance and suppl...

Page 13: ...echanical damage The unit must be transported only in the working position Avoid sharp blows scratches or rough handling during loading and unloading Prior to the initial power up after transportation at low temperatures allow the unit to warm up at operating temperature for at least 3 4 hours Problem Possible reasons Troubleshooting The fan s do es not get started No power supply Make sure the po...

Page 14: ... the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s manua...

Page 15: ...ATE The unit _____________________________________ is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and sta...

Page 16: ...V147 1EN 02 ...

Reviews: