Vents VKMSz 150 User Manual Download Page 6

6

VKMz

www.ventilation-system.com

TECHNICAL DATA

Permitted deviation of mains voltage: ±10 % of the rated voltage.
The fan must be grounded.
Ingress protection rating against access to hazardous parts and water ingress is IPX4.

Fan model

Voltage [V] at 

50 Hz

Power [W]

Current [A]

Max air flow [m

3

/h]

RPM  [min

-1

]

Noise level at 3 m 

[dBA]

Transported air 

temperature [°С]

VKMz 100

1~230

60

0,28

279

2840

40

-25…+45

VKMz 125 

64

0,29

360

2840

40

VKMz 150 E

64

0,29

455

2780

41

VKMz 150

94

0,42

580

2750

45

VKMSz 150 

126

0,55

700

2740

48

VKMz 200

193

0,84

1150

2780

49

Fan model

Voltage [V] at 

50 Hz

Power [W]

Current [A]

Max air flow [m

3

/h]

RPM  [min

-1

]

Noise level at 3 m 

[dBA]

Transported air 

temperature [°С]

VKMz 100

1~230

82

0,36

278

3320

41

-25 +45

VKMz 125 

85

0,37

357

3300

42

VKMz 150 E

80

0,35

490

3040

42

VKMz 150

131

0,58

622

3020

46

VKMSz 150 

175

0,77

739

2960

49

VKMz 200

240

1,05

1200

2850

49

The unit design is constantly being improved, thus some models, their wiring diagrams and terminal symbols may be slightly different 
from those described in this manual.

OVERALL AND CONNECTING DIMENSIONS

Model

Dimensions [mm]

Weight [kg]

 D

 D1

В

В1

L

L1

L2

L3

VKMz 100

99

245

259

299

190

20

20

30

2,7

VKMz 125 

124

245

259

299

190

20

20

30

2,7

VKMz 150 E

149

274

290

330

170

20

20

30

3,5

VKMz 150

149

345

355

395

200

20

20

40

5,1

VKMSz 150 

149

345

355

395

230

20

20

40

5,6

VKMz 200

198

345

355

395

245

25

25

40

6,1

Summary of Contents for VKMSz 150

Page 1: ...VKMz 100 VKMz 125 VKMz 150 VKMz 150 E VKMSz 150 VKMz 200 Centrifugal inline fan USER S MANUAL ...

Page 2: ...slated into any language in any form without the prior written permission of the Company SAFETY REQUIREMENTS Please read the user s manual carefully prior to installing and operating the unit All user s manual requirements as well as the provisions of all the applicable local and national construction electrical and technical norms and standards must be observed when installing and operating the u...

Page 3: ...ng the unit to power mains Do not operate the unit outside the temperature range stated in the user s manual Do not operate the unit in aggressive or explosive environments Do not touch the unit controls with wet hands Do not carry out the installation and maintenance operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not al...

Page 4: ...operation Do not direct the air flow produced by the unit towards open flame or ignition sources Do not block the air duct when the unit is switched on In case of continuous operation of the unit periodically check the security of mounting Do not sit on the unit and avoid placing foreign objects on it Use the unit only for its intended purpose THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ...

Page 5: ...mation of hazardous substances toxic substances dust pathogenic germs THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS...

Page 6: ...nt A Max air flow m3 h RPM min 1 Noise level at 3 m dBA Transported air temperature С VKMz 100 1 230 82 0 36 278 3320 41 25 45 VKMz 125 85 0 37 357 3300 42 VKMz 150 E 80 0 35 490 3040 42 VKMz 150 131 0 58 622 3020 46 VKMSz 150 175 0 77 739 2960 49 VKMz 200 240 1 05 1200 2850 49 The unit design is constantly being improved thus some models their wiring diagrams and terminal symbols may be slightly ...

Page 7: ...ical or horizontal mounting Air motion in the system must be in compliance with the direction of the arrow on the fan casing Install a hood on outlet discharge spigot side in case of the vertical fan installation Provide a straight air duct section at least 1 m long on the intake spigot side in case of horizontal fan installation with maximum allowable humidity m Mounting sequence Remove the bolt ...

Page 8: ...external circuit breaker with a thermal magnetic trip built into the stationary wiring to disconnect all the power mains phases The rated current must be not below the rated current consumption refer to the Technical data section The QF external switch location must ensure free access for quick shutdown of the fan The recommended circuit breaker nominal current is 1 A The recommended wire cross se...

Page 9: ...the fan again Low air flow Clogging of air ducts or other ventilation system elements Impeller clogging Damaged air ducts Air damper closure Clean the air ducts and other ventilation system elements as well as the impeller Check the air ducts for damage Make sure the air dampers and louvre shutters are open STORAGE AND TRANSPORTATION REGULATIONS Store the unit in the manufacturer s original packag...

Page 10: ... Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s manual Us...

Page 11: ...ATION CERTIFICATE The VKMz____ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and standards The unit...

Page 12: ...V05 1EN 09 ...

Reviews: