VKMz 100  

VKMz 125  

VKMz 150 

VKMz 150  E

VKMSz 150 

VKMz 200

Centrifugal inline fan

USER’S MANUAL

Summary of Contents for VKMSz 150

Page 1: ...VKMz 100 VKMz 125 VKMz 150 VKMz 150 E VKMSz 150 VKMz 200 Centrifugal inline fan USER S MANUAL ...

Page 2: ...slated into any language in any form without the prior written permission of the Company SAFETY REQUIREMENTS Please read the user s manual carefully prior to installing and operating the unit All user s manual requirements as well as the provisions of all the applicable local and national construction electrical and technical norms and standards must be observed when installing and operating the u...

Page 3: ...ng the unit to power mains Do not operate the unit outside the temperature range stated in the user s manual Do not operate the unit in aggressive or explosive environments Do not touch the unit controls with wet hands Do not carry out the installation and maintenance operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not al...

Page 4: ...operation Do not direct the air flow produced by the unit towards open flame or ignition sources Do not block the air duct when the unit is switched on In case of continuous operation of the unit periodically check the security of mounting Do not sit on the unit and avoid placing foreign objects on it Use the unit only for its intended purpose THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ...

Page 5: ...mation of hazardous substances toxic substances dust pathogenic germs THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS...

Page 6: ...nt A Max air flow m3 h RPM min 1 Noise level at 3 m dBA Transported air temperature С VKMz 100 1 230 82 0 36 278 3320 41 25 45 VKMz 125 85 0 37 357 3300 42 VKMz 150 E 80 0 35 490 3040 42 VKMz 150 131 0 58 622 3020 46 VKMSz 150 175 0 77 739 2960 49 VKMz 200 240 1 05 1200 2850 49 The unit design is constantly being improved thus some models their wiring diagrams and terminal symbols may be slightly ...

Page 7: ...ical or horizontal mounting Air motion in the system must be in compliance with the direction of the arrow on the fan casing Install a hood on outlet discharge spigot side in case of the vertical fan installation Provide a straight air duct section at least 1 m long on the intake spigot side in case of horizontal fan installation with maximum allowable humidity m Mounting sequence Remove the bolt ...

Page 8: ...external circuit breaker with a thermal magnetic trip built into the stationary wiring to disconnect all the power mains phases The rated current must be not below the rated current consumption refer to the Technical data section The QF external switch location must ensure free access for quick shutdown of the fan The recommended circuit breaker nominal current is 1 A The recommended wire cross se...

Page 9: ...the fan again Low air flow Clogging of air ducts or other ventilation system elements Impeller clogging Damaged air ducts Air damper closure Clean the air ducts and other ventilation system elements as well as the impeller Check the air ducts for damage Make sure the air dampers and louvre shutters are open STORAGE AND TRANSPORTATION REGULATIONS Store the unit in the manufacturer s original packag...

Page 10: ... Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s manual Us...

Page 11: ...ATION CERTIFICATE The VKMz____ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and standards The unit...

Page 12: ...V05 1EN 09 ...