N(3)
Quiet 100/125 Duo TH
Activation of turn-off
delay timer (2-30 minutes)
Fan runs at speed 2
Humidity exceeds
set point
No
Yes
Activation of turn-on
delay timer (60 seconds)
Humidity exceeds
set point
No
Fan runs at speed 1
Contact of the S switch
or the pull cord switch is
CLOSED
Activation of turn-on
delay timer (60 seconds)
Humidity exceeds
set point
Yes
No
Contact of the S switch
or the pull cord switch is
OPENED
Fan runs at speed 2
No
Yes
The contact of the S switch
or the pull cord switch is
OPENED
during the turn-on delay timer
operation
Yes
Humidity is below
set point
20.