• the unit is rated for connection to 1~230 V/50 or 3~400 V/50 (60) Hz power mains.
• the unit must be connected to power mains using insulated electric conductors (cables, wires). the actual wire cross section selection
must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and
installation method.
• the external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric circuit
in case of overload or short-circuit. the circuit breaker installation place must provide quick access for emergency shutdown of the unit.
the trip current of the automatic circuit breaker
QF
must exceed the maximum current consumption of the unit (refer to the technical
data table). the recommended trip current of the circuit breaker is the next current in the standard trip current row following the
maximum current of the connected unit. the automatic circuit breaker is not included in the delivery set.
Connection of
OV, OVK, VKF, OVP
fans with single-phase motor
Connection of
OV, OVK, VKF
fans with three-phase motor
Connection of
OV1, OVK1, VKOM(z), VKOM1(z)
fans with single-phase motor
L
N
X1
1
2
3
N
L
QF
PE
4
L
N
X1
1
2
3
N
L
QF
PE
4
~230 V
50/60 Hz
PE
TW2
TW1
L2
L1
QF
L2
L1
X1
2
1
3
L3
TW1
TW2
4
6
5
L3
PE
TW2
TW1
L2
L1
QF
L2
L1
X1
2
1
3
L3
TW1
TW2
4
6
5
L3
~400 V
50/60 Hz
L
N
X1
1
2
3
N
L
QF
PE
L
N
X1
1
2
3
N
L
QF
PE
~230 V
50/60 Hz
DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED
ELECTRICIAN WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER
CAREFUL READING OF THE PRESENT USER’S MANUAL. THE RATED ELECTRICAL
PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.
CONNECTION TO POWER MAINS
OV1 R fan installation