2
NE MICRA
www.ventilation-system.com
1
Adjust the heater length L in consideration of the air duct length and the vent hood dimensions.
20 mm
L
min 3 mm
Mark the necessary length of the heater L on the guide tube, cut off the extra cable ties with wire cutters, move the cable away to the
side and saw off the redundant part of the tube.
L
2
Trim the drain tube.
The distance between the ends of the drain tube and the guide tube on the temperature sensor side shall be 20 - 30 mm.
20-30 mm
L
The electric heater maintains above-zero temperature of the condensate drain pipe of the air handling unit. The heater is equipped with a
temperature sensor for automatic activation and de-activation. The device is powered via a plug-in cable which connects it to the control
unit of the air handling unit.
Temperature sensor
Cable for connection
to the control unit
Heating element
Guide tube