![Vents MPA 1200 E3 MPA User Manual Download Page 8](http://html.mh-extra.com/html/vents/mpa-1200-e3-mpa/mpa-1200-e3-mpa_user-manual_1002383008.webp)
8
MPA
www.ventilation-system.com
DESIGN AND OPERATING PRINCIPLE
6
The unit allows controlling the air flow, air temperature (preheating) and air filtering.
• Air flow can be adjusted by controlling the fan speed.
• Air heating is provided by an integrated electric heater (item 2).
• The unit is equipped with an air filter with filtering class G4 (item З).
• Hinged (item 4) or removable cover optimally uses the space for installation.
• Unit design allows standard connection to rectangular air ducts of the duct work.
• The unit is equipped with two sensors-thermal switches: one is a safety thermal switch with automatic restart, and the second
one is an emergency thermal switch with manual restart when the RESET button is pressed (pos. 5).
MAIN TECHNICAL PARAMETERS
Model
Voltage
[V] at 50
Hz
Number
of phases
Heater
power
[kW]
Heater
current
[A]
Number
of electric
heating
elements
[pcs]
Fan
power
[W]
Fan current
[A]
RPM
[min
-1
]
Air flow
[m
3
/h]
Sound pressure
level at 3 m
distance [dBA]
Weight
[kg]
Maximum
ambient air
temperature
[°C]
MPA 800 Е1
230
1
3.3
14.3
1
245
1.08
1650
800
35
36.2
45
MPA 1200 ЕЗ
400
3
9.9
14.3
3
410
1.8
1850
1200
38
38.9
45
MPA 1800 ЕЗ
400
3
18.0
26.0
3
490
2.15
1100
1800
40
61.5
45
MPA 2500 ЕЗ
400
3
18.0
26.0
3
650
2.84
1000
2500
45
62
45
MPA 3200 ЕЗ
400
3
25.2
36.4
6
1270
2.3
1200
3200
53
69.4
45
MPA 3500 ЕЗ
400
3
25.2
36.4
6
1270
2.3
1200
3500
53
69.3
45
Summary of Contents for MPA 1200 E3 MPA
Page 1: ...MPA E USER S MANUAL Single block air supply unit ...
Page 16: ...16 MPA www ventilation system com MPA 800 CONTROL UNIT ...
Page 17: ...17 www ventilation system com MPA 1200 2500 CONTROL UNIT ...
Page 22: ...22 MPA www ventilation system com ...
Page 23: ...23 www ventilation system com ...
Page 24: ...V27EN 04 ...