6
KP/PL
www.ventilation-system.com
Overall and connecting dimensions of KP-1...72S dampers with a mechanical actuator
350
А
А1
А2
В
В2
В1
Model
Dimensions [mm]
Weight
[kg]
A
A1
A2
B
B1
B2
KP-1-200x200-2-72S-SN
200
220
240
200
220
240
3.5
KP-1-250x200-2-72S-SN
250
270
290
200
220
240
4
KP-1-250x250-2-72S-SN
250
270
290
250
270
290
4.5
KP-1-300x200-2-72S-SN
300
320
340
200
220
240
4.5
KP-1-300x250-2-72S-SN
300
320
340
250
270
290
5.1
KP-1-300x300-2-72S-SN
300
320
340
300
320
340
5.8
KP-1-400x250-2-72S-SN
400
420
440
250
270
290
6.3
KP-1-400x300-2-72S-SN
400
420
440
300
320
340
7.1
KP-1-400x400-2-72S-SN
400
420
440
400
420
440
8.7
KP-1-500x300-2-72S-SN
500
520
540
300
320
340
8.5
KP-1-500x400-2-72S-SN
500
520
540
400
420
440
10.3
KP-1-500x500-2-72S-SN
500
520
540
500
520
540
12
KP-1-600x400-2-72S-SN
600
620
640
400
420
440
11.9
KP-1-600x500-2-72S-SN
600
620
640
500
520
540
13.8
KP-1-600x600-2-72S-SN
600
620
640
600
620
640
16.1
Dampers with dimensions not included in the table can be produced on request.
TECHNICAL DATA
The dampers are designed for operation in spaces with non-aggressive environment, the air temperature ranging from -30 °C to +45 °C
and relative humidity up to 80 %.
The dampers are compliant with the IPX4 standard (hazardous parts access and water ingress protection).
In terms of electric shock hazard the products belong to the following categories of electrical appliances:
• Class III (low voltage) for the dampers with 24 V electric actuator power supply.
• Class II (complete insulation) for the dampers with 230 V electric actuator power supply.
The dampers may not be integrated:
• Into air ducts and on premises rated explosion and fire safety category A and B.
• Into air ducts of local intakes for flammable and explosive mixtures.
• Into systems which do not undergo periodic cleaning pursuant to an approved schedule to prevent the build-up of combustible
deposits.
The damper undergoes continuous improvement. Therefore, some models may slightly differ from the ones described herein.
Summary of Contents for KP Series
Page 1: ...KP PL USER S MANUAL KP PL Fire resisting duct damper ...
Page 23: ...23 www ventilation system com ...
Page 24: ...V58 1EN 03 ...