USER’S MANUAL

KP/PL

Fire-resisting duct damper

Summary of Contents for KP Series

Page 1: ...KP PL USER S MANUAL KP PL Fire resisting duct damper ...

Page 2: ...d into any language in any form without the prior written permission of the Company Safety requirements 2 Purpose 4 Delivery set 4 Designation key 5 Technical data 6 Design and operating principle 14 Mounting and set up 15 Connection to power mains 19 Technical maintenance 20 Storage and transportation regulations 20 Manufacturer s warranty 21 Certificate of acceptance 22 Seller information 22 Ins...

Page 3: ...rry out the installation and maintenance operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit The unit is allowed to be used by children aged from 8 years oldand above and persons with reduced physical sensory or mental capabilities or no experience and knowledge provided that they have b...

Page 4: ...f openings in supply and exhaust ducts of smoke ventilation systems The dampers of this particular design are not suitable for installation in air ducts and ducts of premises with rated explosion and fire safety category A and B and in flammable and explosive mixture intakes The KP 1 fire resisting duct dampers are capable of resisting fire for at least 60 minutes EI 60 at the temperature of 600 C...

Page 5: ...ator with a return spring and a thermal breaker Actuator location SN outside VN inside Design variant _ ordinary damper design 1 simplified damper design for KP 2 only Designation example PL 10 PKP24T DN100 EI120 Series Normally open fire resisting duct damper with a thermal fuse and a return spring or electric actuator a return spring and thermoelectric breaker Actuator type 1A thermal fuse 72 C ...

Page 6: ... 2 72S SN 600 620 640 600 620 640 16 1 Dampers with dimensions not included in the table can be produced on request TECHNICAL DATA The dampers are designed for operation in spaces with non aggressive environment the air temperature ranging from 30 C to 45 C and relative humidity up to 80 The dampers are compliant with the IPX4 standard hazardous parts access and water ingress protection In terms o...

Page 7: ...0 11 3 KP 1 500x300 2 SN 500 520 540 625 300 320 340 10 7 KP 1 500x400 2 SN 500 520 540 625 400 420 440 12 9 KP 1 500x500 2 SN 500 530 560 635 500 530 560 16 6 KP 1 600x400 2 SN 600 620 640 725 400 420 440 14 5 KP 1 600x500 2 SN 600 630 660 735 500 530 560 18 4 KP 1 600x600 2 SN 600 630 660 735 600 630 660 20 6 KP 1 800x500 2 SN 800 830 860 935 500 530 560 22 3 KP 1 800x600 2 SN 800 830 860 935 60...

Page 8: ...5 3 KP 2 300x300 2 72S SN 300 320 340 380 300 320 340 380 415 18 8 KP 2 400x250 2 72S SN 400 420 440 480 250 270 290 330 515 19 2 KP 2 400x300 2 72S SN 400 420 440 480 300 320 340 380 515 19 7 KP 2 400x400 2 72S SN 400 420 440 480 400 420 440 480 515 22 KP 2 500x300 2 72S SN 500 520 540 580 300 320 340 380 615 22 5 KP 2 500x400 2 72S SN 500 520 540 580 400 420 440 480 615 24 7 KP 2 500x500 2 72S S...

Page 9: ... 480 540 23 3 KP 2 500x300 2 SN 500 520 540 580 300 320 340 380 640 23 8 KP 2 500x400 2 SN 500 520 540 580 400 420 440 480 640 26 KP 2 500x500 2 SN 500 530 560 580 500 530 560 580 650 33 KP 2 600x400 2 SN 600 620 640 680 400 420 440 480 740 32 7 KP 2 600x500 2 SN 600 630 660 680 500 530 560 580 750 38 4 KP 2 600x600 2 SN 600 630 660 680 600 630 660 680 750 43 KP 2 800x500 2 SN 800 830 860 880 500 ...

Page 10: ...400 420 440 12 6 KP 2 500x300 2 SN 1 500 520 540 640 300 320 340 12 3 KP 2 500x400 2 SN 1 500 520 540 640 400 420 440 14 3 KP 2 500x500 2 SN 1 500 530 560 650 500 530 560 23 KP 2 600x400 2 SN 1 600 620 640 740 400 420 440 16 2 KP 2 600x500 2 SN 1 600 630 660 750 500 530 560 25 6 KP 2 600x600 2 SN 1 600 630 660 750 600 630 660 28 6 KP 2 800x500 2 SN 1 800 830 860 950 500 530 560 31 3 KP 2 800x600 2...

Page 11: ... 1А DN315 314 190 327 3 6 PL 10 1А DN355 354 190 367 4 4 PL 10 1А DN400 399 240 412 6 The PL 10 PKP PL 10 PVP PL 10 PSP fire safety damper with an electric actuator and a thermally sensitive breaker D L B Model Dimensions mm Weight kg Ø D L B PL 10 DN100 99 300 195 2 9 PL 10 DN125 124 300 215 3 1 PL 10 DN150 149 300 245 3 4 PL 10 DN160 159 300 255 3 5 PL 10 DN180 179 300 275 3 8 PL 10 DN200 199 30...

Page 12: ...ree Running time spring 20 seconds at 10 55 C 60 seconds at 30 10 C 16 seconds at 20 C Running time motor 60 s 90 120 s 90 Response temperature of thermal breaker sensors Duct sensor 72 C Outdoor sensor 72 C Service life Min 60 000 emergency positions Technical maintenance Not required Main technical specifications of Zern electric actuators with a return spring and a thermal breaker Technical dat...

Page 13: ...rest W 2 3 5 2 3 5 3 4 Power consumption in operation W 3 5 4 5 3 5 4 5 5 6 Maximum design capacity VA 5 7 5 7 7 8 Motor torque Nm 4 9 18 Spring torque Nm 4 7 18 Protection class III II III II III II Ingress protection rating IP54 Auxiliary switches 2 pcs single pole reversible 6 2 A AC 24 250 V Electric motor connection cable 0 9 m 2 x 0 75 mm halogen free Auxiliary switch connection cable 0 9 m ...

Page 14: ...ctuator and thermoelectric breaker Casing Electric actuator Seal Hot and cold zone baffle Damper swing mechanism Air damper Thermoelectric breaker The KP 2 PKP 1 KP 2 PVP 1 KP 2 PSP 1 fire safety damper with a Belimo electric actuator and thermoelectric reaker Casing Electric actuator Damper swing mechanism Air damper Thermoelectric breaker Casing perforation Ceramic fibre and aluminium foil tape ...

Page 15: ...ety zone KP DAMPER INSTALLATION The dampers can be installed in any position into vertical and horizontal channels of fire protection structures The damper installation openings must be made in such a way so as to prevent the transfer of loads caused by the fire protection structures to the damper casing The adjoining air duct must be suspended in such a way so as to prevent the transfer of air du...

Page 16: ...ermediate layer INSTALLATION RECOMMENDATIONS FOR KP 1 PKP KP 1 PVP KP 1 PSP FIRE SAFETY DAMPERS WITH ELECTRIC ACTUATOR AND THERMOELECTRIC K W 270 K W Wall fire separation Intermediate Layer Ceiling fire separation Fire resisting damper with an electrical actuator Fire resisting damper with an electrical actuator Intermediate layer INSTALLATION RECOMMENDATIONS FOR KP 2 72S DAMPERS WITH A THERMAL FU...

Page 17: ...r Fire resisting damper with an electrical actuator Fire resisting damper with an electrical actuator K W Ceiling fire separation Insulation INSTALLATION RECOMMENDATIONS FOR KP 2 PKP 1 KP 2 PVP 1 KP 2 PSP 1 FIRE SAFETY DAMPERS WITH AN ELECTRIC ACTUATOR AND THERMOELECTRIC BREAKER А А 160 В В 160 K W Wall fire separation Intermediate layer Intermediate layer K W Ceiling fire separation Fire resistin...

Page 18: ...g damper with an electrical actuator Fire safety dampers can be installed into solid ceiling panels with the minimum thickness of W 150 mm minimum intermediate layer thickness S 50 mm The ceiling panels are made of concrete The intermediate layer can be made of concrete or mortar While carrying out the installation mind size K When installing the dampers into thicker walls add an extender section ...

Page 19: ...rmediate positions of the damper are shown by the mechanical indicator needle The BF24 T and BFN24 T actuators are connected via an insulated transformer unit The damper can also be controlled manually and fixed in any position The unit can be unlocked either manually using a hex wrench included or automatically upon power up The actuator connections cables and wires must be durable insulated and ...

Page 20: ...n the working position Avoid sharp blows scratches or rough handling during loading and unloading Prior to the initial power up after transportation at low temperatures allow the unit to warm up at operating temperature for at least 3 4 hours The damper technical maintenance includes routine inspections and functionality checks The damper technical maintenance frequency must comply with the establ...

Page 21: ...epair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component The warranty repair does not include routine technical maintenance unit installation dismantling unit setup To benefit...

Page 22: ...CATE The KP PL __________________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and...

Page 23: ...23 www ventilation system com ...