DO NOT USE A METAL SCREWDRIVER, KNIFE, ETC. FOR ADJUSTMENT
OPERATIONS NOT TO DAMAGE THE CIRCUIT BOARD.
FAN SETUP
: to adjust the humidity set point turn the control knob H clockwise to increase and counter-clockwise to decrease the
humidity sensor set point, adjustable from 60% up to 90%.
: turning of the interval timer on and its adjustment is performed with the potentiometer
T
i
. To turn the interval timer
off, set the potentiometer
T
i
into the leftmost position. Rotation of the potentiometer for 1/3 clockwise sets the interval timer
operation for 6 hours, rotation of the potentiometer for 2/3 clockwise sets the interval timer operation for 12 hours, rotation
of the potentiometer clockwise in the rightmost position sets the interval timer operation for 24 hours.
: to adjust the fan turn-off delay time, turn the control knob
T
of
f
clockwise to increase and counter-clockwise to
decrease the turn-off delay time respectively, adjustable from 2 up to 30 minutes.
Attention! If the switch opens within 60 seconds after its closing, the fan operating status does not change.
Attention! After closing of the switch S the front
panel opens within 1 minute. After opening of
the switch S (for basic model) or after countdown
of the turn-off delay time (for T and TH models)
the front panel closes within 1 minute.
The fan delivery set includes a specially designed
plastic screwdriver for fan settings adjustments.
Use it for setting the on-delay time, off-delay time and
humidity setpoint.
H
60%
90%
T
off
2 min
30 min
T
i
Off
24 hour
for H
for Т
for Т/TH
Summary of Contents for 100 Style Eco
Page 1: ...AXIAL FAN User s manual www ventilation system com EN Vents 100 Style...
Page 12: ...12 EN 175 140 77 67 221 188 50 123 55 99 39 1 2...
Page 13: ...13 EN QF L N 3 4 5 6 7 8 9 10 11...
Page 18: ...18 EN QF L N 17 18 19 20...
Page 19: ...19 EN Approval mark Manufacturing date Sold name and stamp of the seller Sales date...