CIRCULAR DUCT WATER HEATERS
CWC/CWH
2
The duct water heaters CWC/CWH with circular duct connections are designed for
heating/cooling the ventilation air in a ventilation system. The CWH/CWC can also be used for heating
or cooling individual rooms or zones. For controlling the room or supply air temperature, the duct
heaters can be supplemented with regulators, sensors, actuators, valves and anti-freeze protection.
➢
9 standard sizes (9 heaters and 9 coolers);
➢
Water coils with 2 or 3 tube rows (cooler with 3 rows only);
➢
Casing of Aluzinc coated sheet steel, AZ 150;
➢
Openable cover for inspection and cleaning;
➢
Circular duct connections with rubber seals;
➢
Air tightness class D to EN 15727;
➢
Coils are used with water (
0/+110°C
), as well as glycol (-
40/110°C
);
➢
➢
CWH
125
-
2
1
2 3
1- Type
CWH
–
Circular water heater
CWC
–
Circular water cooler
2
–
Duct diameter (mm)
100
–
100 mm
315
–
315 mm
125
–
125 mm
355
–
355 mm
160
–
160 mm
400
–
400 mm
200
–
200 mm
500
–
500 mm
250
–
250 mm
3
–
Number of tube rows
2
–
2 rows
3
–
3 rows
➢
Operating temperature range: 0/+11
0°C
(water); -40/110
°C
(glycol)
➢
Max. operating pressure: 1,6 MPa (16 bar)
➢
The coils are tested for leakage (Bubble test described in the EN 1799)
Description
Operating data: water coil
Model marking