background image

Page 4

L114A 0808A

Wall Cutout for Horizontal Ducting

Viewed from Front

Bottom of 

Cabinet

3⁄8"

3 ½"

5 1⁄8"

5 1⁄8"

6 ¼"

1 1⁄8"

Electrical

CL

Installation Details Continued

6)  Remove the hood from its packaging and place on the floor or countertop in front of the cabinet where it will hang.

Warning:  Do not operate hood without  proper ground connection.

Warning:  Make sure power is off and locked at the service disconnecting 

means on the service panel during installation.

7)  Determine whether the electrical wire will enter from the top or the back of the hood. Remove the electrical enclosure 

cover (1 screw) and the top or back electrical enclosure knockout from the hood. Install an appropriate 1/2” UL listed 
electrical  wire  clamp  through  the  electrical  knockout.  Install  electrical  wiring  from  the  electrical  panel  to  the  hood 
location.

8)  Insert the electrical wire through the electrical wire clamp allowing 3” - 4” of wire inside the enclosure for hookup.  

Tighten the electrical wire clamp.

9)  From inside the hood, using UL listed wire nuts, attach the “neutral” wire to the white lead, the “hot” wire to the black 

lead, and the ground wire to the green lead inside the junction box. Replace the electrical cover previously removed 

in Step 7.

10) FOR BACK VENTING APPLICATIONS ONLY. IF YOU ARE NOT BACK VENTING, PROCEED DIRECTLY TO STEP 12.

 

Note:  Wall studs may interfere with back venting installations. 
Additional framing may be required.  It is necessary to cut a 
duct access hole in the wall prior to installing the hood. Starting 
2 1/8” above the bottom edge of the hood, cut a hole 3 1/2” 

high x 10 1/4” wide (see diagram at right).

11)  Install the duct from the outside of the home to the duct access 

hole in the wall. Where possible, use duct tape to seal joints.

12) While  aligning  the  duct  and  guiding  the  wires,  position  the 

hood  under  the  cabinet.  The  duct  should  connect  together 
as the hood is located in place. Note: Unless using the VP521 

transition, the duct work must fit inside the exhaust collar. If 

using the VP521, 7” round duct should be placed with the non-

crimped end on the outside of the collar of the VP521 exhaust 

outlet. Using the four screws provided, attach the hood to the 
bottom of the cabinet.

14) Refer to the Owner Maintenance Guide Operating Instructions for proper hood operation. Test all blower and light 

functions to ensure they are operating properly.

Model

Volts

Amps

Hz

RPM

CFM

[email protected]" Equivalent CFM

CFM

[email protected]"

CFM

[email protected]"

CFM

[email protected]"

Minimum Round

Duct Size

Sones

#

K250 (Top Vent)

115

3.2

60

1550

250

375

223

220

190

7" (38 in.

2

)

7.4

K250 (Back Vent)

115

3.2

60

1550

220

330

196

194

167

7" (38 in.

2

)

7.4

  Because the Magic Lung

®

 blower uses centrifugal filtration rather than conventional baffle or mesh filters, the Magic Lung

®

 blower can handle cooking equipment with higher cubic feet per minute (CFM) requirements and can deliver equivalent CFM much more 

efficiently than other than other filtration systems. When comparing the Magic Lung

®

 with other blower units made by other manufacturers, use the “Equivalent CFM”.

#

  Ratings in accordance with the Standard Test Code by the Energy Systems Laboratory of the Texas Engineering Experiment Station.

Summary of Contents for SLH6-K

Page 1: ...he service disconnecting means to prevent power from being switched on accidentally during installation B When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities C Ducted fans must always be vented to the outdoors D Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent ba...

Page 2: ...angled turns Instead use smooth gradual turns such as adjustable elbows or 45 degree angled turns For duct runs over 20 feet increase the duct diameter by one inch for every ten feet of duct A 90 degree elbow is equal to 5 feet of duct Using Vent A Hood roof jacks or wall louvers back page will ensure proper efficiency Airflow must not be restricted at the end of the duct run Do not use screen wir...

Page 3: ...izontal discharge by exchanging the discharge adapter on top of the hood 4 screws with the discharge cover on the back of the hood 2 screws Use duct tape to seal the discharge adapter and discharge cover to the hood 5 IF THE HOOD IS TO BE BACK VENTED PROCEED DIRECTLY TO STEP 6 Install the duct from the outside of the home down to the location of the hood exhaust outlet allowing room for the VP521 ...

Page 4: ... wall prior to installing the hood Starting 2 1 8 above the bottom edge of the hood cut a hole 3 1 2 high x 10 1 4 wide see diagram at right 11 Install the duct from the outside of the home to the duct access hole in the wall Where possible use duct tape to seal joints 12 While aligning the duct and guiding the wires position the hood under the cabinet The duct should connect together as the hood ...

Page 5: ...9 3 x 10 4 10 14 3 3 MULTI BLOWER TRANSITION MODEL DIM VP562 VP563 6 8 to 10 8 8 to 12 VP562 17 VP563 16 10 12 VP562 23 VP563 30 3 x 10 TO 7 TRANSITION MODEL DIM VP521 3 x 10 to 7 7 7 3 10 LOW PROFILE ROOF JACK MAXIMUM 4 12 PITCH MODEL DIM 6 VP539 VP540 VP541 6 Round 7 Round 8 Round 16 16 LOW PROFILE ROOF JACK MAXIMUM 4 12 PITCH MODEL DIM 10 VP552 VP553 10 Round 12 Round 22 20 ADJUSTABLE ELBOW MOD...

Reviews: