IMPORTANT SAFETY INFORMATION
1. DO NOT install this product in areas where the following may be present or occur:
2. Excessive oil or a grease laden atmosphere.
3. Corrosiveorflammablegases,liquidsorvapours.
4. Subject to direct water spray from hoses.
5. Ambient temperatures higher than 40°C or less than –20°C.
6. Possible obstructions which would hinder the access or removal of the Fan.
7. AllwiringmustbeinaccordancewiththecurrentIEEwiringregulationsBS7671,or
appropriate standards of your country. Installation should be inspected and tested by a
suitablyqualifiedpersonaftercompletion.
8. Ensurethemainssupply(voltage,frequencyandphase)complieswiththeratinglabel.
9. A means for electrical disconnection must be incorporated in the fixed wiring to the unit
in accordance with the wiring rules having a contact separation in all poles of at least
3mm.
10. These units must be earthed.
11. Precautions must be taken to avoid the back-flow of gases into the building from the
open flue of gas or other fuel-burning appliances.
12. Thisapplianceisnotintendedforusebypersons(includingchildren)withreduced
physical,sensoryormentalcapabilities,orlackofexperienceandknowledge,unless
they have been given supervision or instruction concerning use of the appliance by a
person responsible for their safety.
13. Young children should be supervised to ensure that they do not play with the
appliance.
14. CAUTION: In order to avoid a hazard due to inadvertent resetting of the thermal cut-
out,thisappliancemustnotbesuppliedthroughanexternalswitchingdevice,suchas
atimer,orconnectedtoacircuitthatisregularlyswitchedonandoffbytheutility.
15. These units are rated IP22 and are not suitable for outside use.
INSTALLATION GUIDANCE:
1. The installer is responsible for the installation and electrical connection of the system on site. It is the responsibility
oftheinstallertoensurethattheequipmentissafelyandsecurelyinstalledandleftonlywhenmechanicallyand
electrically safe.
2. Shortductrunsterminatingclosetothefan(i.e.within1.5m)requiresuitableguards.
3. Allregulationsandrequirementsmustbestrictlyfollowedtopreventhazardstolifeandproperty,bothduringand
afterinstallation,andduringanysubsequentservicingandmaintenance.
4. Certainapplicationsmayrequiretheinstallationofsoundattenuationtoachievethesoundlevelsrequired.
5. SLPECunitsaredesignedandspecifiedforusewithVent-Axiacontrols,dampers,grillesandaccessories.
6. Allmainsconnectionstotheunitusingflexiblewiringoranyadditionalcontrolswiringmustusecableglands
sufficienttoretaintheIPratingoftheunitandprovidecableretentiontotherequirementsofEN60335-1
Clause 25.15.
7. Thefixingsandanchorsusedtosuspendandmounttheunitmustbecompatiblewiththeunit’sweight.
Suitable drop rods and anti-vibration mounts can be used.
8. Due to the weight of the units it is recommended that two people are involved in the installation.
9. Itisrecommendedthatflexibleconnectionsareusedbetweentheunitandrigidducting.
IMPORTANT: READ THESE INSTRUCTIONS
BEFORE COMMENCING THE INSTALLATION