Commissioning 

Sentinel Kinetic MVHR Installation & Commissioning 

26

 

Proportional 2 Screen 

By default, the Proportional 2 input is set to CO

2

 sensor 

operation. 

See 

Proportion 1 Screen

 for a description.  

Proportional   2 
CO2 

 

Momentary closure (1 sec) starts or stops boost for set 
time. 

Selectable range: min. = 

15

, max. = 

30

Default = 

Off

 when no Vent-Wise card fitted. 

SW4 Momentary 
Off 

Vent-Wise Screens 

These screens are only displayed if a Vent-Wise Card is fitted. Replacing J6 3-4 link with a Vent-Wise board 
converts S/W1, S/W2 and S/W3 from switch inputs to Vent-Wise inputs.  In addition SW4 can be used by a 
momentary switch. (The Vent-Wise board must be fitted the correct way round refer to instructions supplied with 
the module 441780 for guidance). 

Vent-Wise sensors measure current or temperature.  When the current or temperature exceeds a ‘trip’ level, 
boost airflow is selected. Low / Normal airflow is resumed after a timed delay once the current or temperature 
has dropped below the trip level. 

Any of the sensor types can be connected to S/W1, S/W2 or S/W3 but once the Vent-Wise Card is fitted, 
ordinary switches must not be used. 

In use, the Vent-Wise Card with three sensors will run hot to the touch albeit well below its maximum 
temperature. If any input is shorted (e.g. used with switch), the board will overheat and shut down. 

Nominal trip level is with the Load Pot set to (60 %). A temperature sensor will trip with hot water at around 40

º

and a current one around 1.5 A. Time Pot setting is from 1 to 25 minutes with a default of 20 minutes. 

A one-second push on a momentary switch wired to SW4 will run boost for up to 25 minutes.  The overrun timer 
can be set from 15 to 30 mins.  A second one-second push will cancel the boost as would a “cancel boost” 
signal from one of the sensors. Multiple momentary switches may be wired in parallel to SW4. 

Screens for each of the three switches are displayed. 
Enter a percentage value for the Load Pot setting. 

* Shows Vent-Wise signal and indicates the unit is  
running in Boost mode 

Selectable range: min. = 

5

, max. = 

95

, default = 

60

Ventwise Input 1 
Load Pot 60 % * 

Enter a time (in minutes) for the Time Pot setting.  

Selectable range: min. = 

1

, max. =  

25

, default =  

20

 

Ventwise Input 1 
Time Pot 20 m 

 

Ventwise Input 
nn% 

Momentary closure (1 sec) starts or stops boost for set 
time. 

Selectable range: min. = 

15

, max. = 

30. 

D

efault = 

25

 when Vent-Wise card fitted 

SW4 Momentary 
25 

 
 

 

 

 
 

 

 

SW4 Screen 

 
 

 

 

 
 

 

 

 
 

 

 

Summary of Contents for Sentinel Kinetic 200Z

Page 1: ...009 Vent Axia Limited All rights reserved Sentinel Kinetic 200Z 200ZH 300ZH Installation Commissioning Model Stock Ref N 200Z 448733A 200ZH 449540A 300ZH 449536A PLEASE RETAIN THESE INSTRUCTIONS WITH...

Page 2: ...g children should be supervised to ensure that they do not play with the appliance INSTALLATION GUIDANCE 1 The installer is responsible for the installation and electrical connection of the sentinel s...

Page 3: ...ng 19 Overview 19 Commissioning Screens 20 Maintenance 30 Filter Maintenance 30 12 Monthly Maintenance 30 Spares 33 Troubleshooting 34 Diagnosing a Problem 34 Appendix Options and Accessories 35 CO2 T...

Page 4: ...om If the room is cooler than the set indoor temperature i e you need the room heating and the outdoor air is warmer than the actual room temperature i e the outdoor air could heat your room then the...

Page 5: ...See Graph below Power AC Voltage Input 220 240 V AC single phase AC Frequency Input 50 Hz nominal Supply Fuse 3 A located in fused spur Product Fuse 2 A located on main PCB Rated Power 175W max 180W m...

Page 6: ...unting brackets and product documentation Lift and Move the Unit Safely Check the weight of the unit that you are installing Always use appropriate lifting techniques and appliances when moving heavy...

Page 7: ...ng Mounting Fix the 2 Brackets to the ceiling the fixings must be suitable for the surface type intended concrete wood they must also be compatible for the units weight 200 Z ZH 26 5Kg 300ZH 38 5Kg 20...

Page 8: ...fully tighten Leave approximately a half turn loose on each of the fixings This will allow each bracket to be moveable until final fitting of the unit and makes any adjustments easier while installing...

Page 9: ...e configuration 32mm 22mm waste For installations in a ceiling void where it is too shallow for a traditional U Trap configuration Our recommendation is to use a HepVO inline waste valve and Tundish A...

Page 10: ...Airflow Intake Air from atmosphere Airflow Exhaust Air to atmosphere Attaching the ducting 1 Always use a short piece of flexible ducting 100 150mm long extended to its full length when connecting to...

Page 11: ...end user or used for commissioning the unit 2 Fit the 15 metre Remote Control cable plug into the cable socket fitted to the Heat Recovery Unit 3 Connect the cable assembly to the Remote Control termi...

Page 12: ...ed to be switched by a current detector for example detecting a hob being switched on or a temperature sensor for example detecting the flow of hot water Terminal 4 can be used in conjunction with a m...

Page 13: ...unit fault See the Control Panel for fault code see Service Fault Code Screens on page 34 L Mains Live 220 240 V AC 50 Hz input N Mains Neutral 220 240 V AC 50 Hz input EARTH Mains Earth Earthing con...

Page 14: ...Turn the power off at the mains supply isolator Wired Remote Control Display Display Normal Airflow 30 Buttons Four buttons on the Control Unit provide the controls for configuring and monitoring the...

Page 15: ...a percentage of the unit s maximum flow Airflow Units Wireless Control Screen Not available Wireless Control Not Fitted Humidity Sensor Screen The Humidity Sensor screen displays whether the humidity...

Page 16: ...n be triggered from the wireless transmitter boost switch If the installation has switch sensors is wired to the lighting has Vent Wise sensors Vent Wise momentary switch or if the internal time switc...

Page 17: ...t Clock Screen From the Normal Airflow screen simply press the button once to access the Set Clock screen The Set Clock Control screen enables you to change the clock settings The clock retains its se...

Page 18: ...o on Indoor Temp 25 C Outdoor Temp Screen From the Normal Airflow screen simply press the button until the Indoor Temp is displayed Press button to choose the required temperature and then press butto...

Page 19: ...ooting on page 34 Follow good practice when commissioning the unit Ensure that the system is installed according to the system designers intent incorporating any acoustic ducting that all joints are a...

Page 20: ...ly 20 Low Extract 20 Ckr Hood Supply 30 Ckr Hood Extract 100 Boost Overrun 15 m Boost Delay 00 m Boost On Off Mon1 00 00 00 00 Boost On Off All Set Humidity Sensor Off Normal On Off Mon Normal On Off...

Page 21: ...If a security PIN code has been previously set this screen will display Enter the PIN using and buttons Security PIN Note 1 Whilst displaying the Low Normal Boost Supply Low Normal Boost Extract scree...

Page 22: ...e Normal speed cannot be set below Low speed or above Boost speed setting Normal Extract 30 Low Supply Screen The Low Supply screen enables you to set the Low airflow speed for the Supply fan in order...

Page 23: ...00 m Boost On Off Screen The Boost On Off screen enables you to set a time for boost to be activated for each day of the week You can set up to three On Off times per day shown as Day1 Day2 and Day3 I...

Page 24: ...2 sec will copy yesterday s times to today Setting finishes when the last off minutes for Sun are accepted at which point the screen will now show All Set or holding the button for 3 seconds Normal O...

Page 25: ...e Boost Limit the unit runs at boost airflow Between these limits the unit runs at a proportional airflow Proportional 1 Humidity For a humidity sensor a percentage value must be entered for boost and...

Page 26: ...dinary switches must not be used In use the Vent Wise Card with three sensors will run hot to the touch albeit well below its maximum temperature If any input is shorted e g used with switch the board...

Page 27: ...for 15 minutes hour and run for 45 depending on the temperature below 0 C If the supply air temperature is 20 C or below the supply fan switches off and the extract fan continues to run at reduced ra...

Page 28: ...off for example in conjunction with a smoke alarm No changes may be made to this screen BMS 00 The Security PIN screen enables you top set a four digit personal identification number PIN to access th...

Page 29: ...off inactive Normal On Off All days set to 0 00 on 00 00 off inactive Set Service No Not set Humidity 70 Proportional 1 Humidity Boost Normal 60 CO2 Boost 2000 ppm Normal 1000 ppm Temperature Boost 2...

Page 30: ...sing a vacuum cleaner if necessary 3 Replace the filters and cover plates 4 Reset the automatic message press and hold the and buttons for 5 seconds 12 Monthly Maintenance Item Action Fan Filters Inte...

Page 31: ...te the mains power supply and remove the Filter access Panels and Filters Undo the securing screws and remove the Cover Stage 2 Loosen the Condensate Pipe Jubilee Clip and remove Pipe from Condensate...

Page 32: ...Caution Keep the Tray as horizontal as possible as this may contain condensate Stage 5 Remove the two Heat Exchanger fixing Brackets and Heat Recovery Cell Note Take care when removing the Heat Recov...

Page 33: ...and attention is retained in re applying all fixings to their previous locations Spares The following spares can be ordered from Vent Axia Description Part No 200Z 200ZH Part No 300ZH Filters 2 per p...

Page 34: ...Table 4 Fault Codes The Room Too Cold screen displays the status of the fan If the heating system in the building fails or is switched off and the internal temperature drops below 5 C the unit will st...

Page 35: ...ally depending on the temperature and relative humidity levels in the extracted air whilst avoiding nuisance tripping at night time when temperatures drop and relative humidity naturally rises The uni...

Page 36: ...5 Control Typology Local Demand Control Local Demand Control Local Demand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...n subjected to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage p...

Reviews: