Vent-Axia Lo-Carbon Responce Series Installation And Wiring Instructions Download Page 10

operation the fan enters calibration mode to determine the most efficient 
mode of operation.  
 

Calibration Reset 

In some circumstances it may be necessary to reset the calibration 
settings (if the fan was covered to prevent dust/damage/or poor weather 
outside).  
Reset the calibration by configuring the fan for wall or duct mode (F-0 or 
F-1), turn the product off and on and re-configure back to CV mode  
(F-2). The fan will calibrate after 15 minutes or by holding the pullcord for 
5 seconds.  
 

Pullcord 

  Switches the fan from trickle to boost (for boost overrun time) 

o

  If the overrun time has been set to 0 (disabled), a default 

overrun duration of 5 minutes will take place. 

  This will override LS comfort mode, boosting the fan immediately 

  An activation when a Pullcord/LS (Light Switch) boost is already 

active shall cancel overrun timer (RH boost sources remain 
unaffected) 

 
 

Data Logger Menu 

* When the display is rotated the decimal point will no longer display; eg. 
055 represents 5.5KWh 

 
 

 

 
 
Cutting the power to the fan will not erase the stored data. 

To reset 

the data, hold pullcord for 14 seconds while in the data logger menu.  

 
 

Display text 

Description 

tot run 00y 00d 

Total run time in years and days 

Tri run 00y 00d 

Trickle speed run time in years and days 

Boo run 00d 

Boosted run time in days 

rhu run 00d

 

 

Humidity boosted run time in days 

 

tot EnErgy 00.0 

Total Energy used displayed in KWh* 

24h EnErgy 00 

Energy used in last 24 hours displayed in Wh 

Summary of Contents for Lo-Carbon Responce Series

Page 1: ...tructions Stock Ref N 494143 Response 7 494144 Response 7 Pro 494150 Response 7 SELV 494149 Response 7 Pro SELV PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTION...

Page 2: ......

Page 3: ...installation within Zones 1 2 C The Fan should be provided with a local isolator switch capable of disconnecting all poles having a contact separation of at least 3mm D Ensure that the mains supply V...

Page 4: ...the fan to suit its installation The display is also used to show the day logger and power run meter The fan can be wall window or panel ceiling mounted ACCESSORIES not supplied WALL FITTING KIT A ran...

Page 5: ...lace the front panel EXTERIOR WALL MOUNTING 1 For wall mounting cut a 117mm diameter hole through the wall and insert the wall sleeve Slope the sleeve slightly downwards away from the fan Where necess...

Page 6: ...enclosed or covered with insulation The fan is a class ll double insulated product and MUST NOT be earthed 1 Select and follow the appropriate wiring diagram Fig 1 2 3 or 4 5 6 2 Check all connection...

Page 7: ...ll run for 15 minutes first showing the day logger then cycling between displaying Airflow rate Pro models only other models display speed setting Estimated duct pressure Pro models only Current RH HT...

Page 8: ...c n normal LS overrun c Y comfort mode c n unl Enable disable lock code loc lock code enabled unl lock code disabled unlocked unl Menu lock code Up down selects current digit X moves to next digit 10c...

Page 9: ...d rise function to detect rapid rises in humidity when the ambient rH is under the threshold setting If a rapid rise is detected the fan will increase in speed proportionally between the trickle and b...

Page 10: ...errun duration of 5 minutes will take place This will override LS comfort mode boosting the fan immediately An activation when a Pullcord LS Light Switch boost is already active shall cancel overrun t...

Page 11: ...press of the Mode button will return the fan to the commissioning menu D SERVICING AND MAINTENANCE WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING MAINTE...

Page 12: ...us boost 1 with no trickle facility The fan is internally fused Fig 3 Continuous trickle with boost facility The fan is internally fused Fig 1 Continuous trickle with boost via pull cord The fan is in...

Page 13: ...facility SELV models Fig 6 Continuous trickle with boost facility via LS or internal pullcord SELV models Fig 4 Continuous trickle with pullcord boost SELV models N L 1 Phase Supply 220 240V 50Hz FUSE...

Page 14: ...g the controls Pull front panel as shown Loosen screws DO NOT REMOVE FROM GRILLE the screws are self retaining Pull inner grille away from housing as shown Open up the internal cover to access the spi...

Page 15: ......

Page 16: ...oduct rating label attached to the unit Has not been subjected to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUAR...

Reviews: