Vent-Axia EUROFLOW KDF Series Installation And Wiring Instructions Download Page 2

VENT-AXIA EUROFLOW FANS INSTALLATION AND WIRING INSTRUCTIONS

IMPORTANT - READ THESE INSTRUCTIONS FULLY BEFORE COMMENCING

 

INSTALLATION

4. Plan  the  installation  carefully,  taking  into

consideration  the  important  points  noted  above.

Ensure there is adequate clearance for the hinged,

swing down access door.  Securely mount the fan

via the fixing holes in the fan casing using appropriate

anti-vibration mounts, screws, bolts, rubber bushes,

studding etc.

GENERAL WIRING

WARNING

-  ISOLATE MAINS SUPPLY BEFORE MAKING

    CONNECTIONS

- THIS EQUIPMENT MUST BE EARTHED

The  motor  thermal  protector  (TK)  MUST  be

connected into the control circuit.

1.  All  electrical  connections  should  be  made  by  a

properly qualified electrician.

2.  Remove  the  terminal  box  cover  to  expose  the

terminal  block.  Pass  the  supply  cable  through  a

grommet or cable gland (not supplied) in the terminal

box and make the connections as

indicated on the terminal marker label.

3.  If  using  a  Vent-Axia  speed  controller,  the  speed

controller should be supplied from the isolator switch.

NOTES ON RUNNING

Before switching on CHECK:

1. All mountings are secure.

2. Circuit protection devices are fitted.

3. Earth connections have been made and are secure.

ROUTINE INSPECTION/MAINTENANCE

THIS MUST BE UNDERTAKEN BY A COMPETENT

PERSON.

ISOLATE UNIT FROM ELECTRICAL SUPPLY AND

ENSURE  THAT  IT  CANNOT  BE  ACCIDENTALLY

TURNED BACK ON.

1. We  recommend  that  after  three  months  the  fan

should be inspected and cleaned to ensure there is

no build up of dirt or other deposits on the impeller

or  motor.    Thereafter,  it  should  be  checked  and

cleaned periodically as experience dictates, or at

least twice a year. Please take care not to dislodge

any balancing weights fitted on the fan blades.

If the fan is handling dust laden air, we recommend

that a filter is fitted to the system (suitable filters are

available from Vent-Axia Ltd.).

2. All Vent-Axia EUROFLOW fan motors are fitted with

sealed for life bearings and therefore do not require

lubrication.

3. Check all fasteners and guards are secure.

1. Ensure that the mains supply voltage, frequency,

number of phases and power rating comply with the

details on the rating label.

2. All wiring must be in accordance with current I.E.E.

wiring  regulations,  (BS7671),  or  the  appropriate

standards in your country. The equipment should

be  provided  with  a  local  all  pole  isolator  switch

having a contact separation of at least 3mm.  We

recommend that wiring to the equipment terminal

box be made in flexible conduit to facilitate easy

maintenance.

3. This equipment must be earthed.

4. Ensure safety regulations and practices are adhered

to when installing and using this equipment.

5. When the fan is used to remove air from a room

containing  a  fuel  burning  appliance,  the  installer

must ensure that air replacement is adequate for

both the fan and the fuel burning appliance.  If a fan

is used to supply air into a room, the installer must

ensure that the fan intake is located at least 600mm

away from any flue outlet.

6. This equipment should not be used where it is liable

to be subjected to water spray from hoses, etc., or

where  duct  ambient  temperatures  may  exceed

40

O

C.

7. When the fan is used to handle moisture laden air,

a suitable condensate trap and drainage system

must be incorporated to ensure safe and healthy

operating conditions.

8. When wiring in conjunction with a speed controller,

a 5 step auto-transformer is recommended to ensure

low noise levels.

9.  The  motor  thermal  protector  (TK)  MUST  be

connected into the control circuit.

DESCRIPTION

The EUROFLOW range of forward curved in-line fans

are  designed  to  be  positioned  between  lengths  of

ducting.  The design incorporates an inspection cover

for easy maintenance.

FAN MOUNTING

1. The fan is designed as an in line duct fan to be

positioned between lengths of ducting. Short duct

runs terminating close to the fan (i.e. within 1.5m)

require suitable guards.

2. The fan is supplied with flanges of Euronorm size

for ease of connection to the ductwork system.

3. The fan is suitable for mounting at any angle with the

fan  supported  via  the  mounting  holes  in  the  fan

casing. The use of flexible connectors at the fan inlet

and outlet is recommended to reduced noise and

vibration.