11 - Timer Models 
 
 
 
 
 
 
 

13 

14 
 
 
 
 
 
 

+

-

3

25mins

B. 

WIRING.

 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM 
THE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE. 

 

 

THE ACM FANS ARE DOUBLE INSULATED AND CARRY A        MARK. THERE ARE NO EARTH TERMINALS 
AND THESE FANS MUST NOT BE EARTHED. 

 

1.  Remove terminal box cover & screws and put to one side Fig. 9 
2.  Select and follow the appropriate wiring diagram (Fig. 10-11). 
3.  Check all connections have been made correctly and ensure all terminal connections and cable clamps are 

securely fastened. 

4.  The cable entry must be made using the cable grommet provided 
5.  Replace terminal box cover & screws Fig.12 
6.  Ensure the impeller rotates and is free from obstructions Fig 13 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 
 

 

 
 
 
 

 

 

    N.B:- The Timer fans are factory set for high speed operation in terminal 

LA

 

    for low speed operation the blue wire in the 

LA

 terminal needs to be moved into terminal 

LB 

    (Timer models are not speed controllable) 

 
 

 

 

 

Timer Adjustment. 
 

Two speed with adjustable overrun timer (Factory set 
at high speed LA). The fan must be wired to a remote 
switch (e.g. light switch). When switched ‘ON’, the 
fan will operate at the selected speed, and will 
continue to run for a preset time after the fan is 
switched ‘OFF’. The timer is factory set at 15 minutes 
approx The overrun time period can be adjusted from 
3-25 minutes by altering the adjuster on the control 
PCB. Fig 14. 

 

Before adjusting the timer, switch off the Mains Supply. 

 

Remove the fan terminal box cover and retain screws 
To REDUCE the operating time, turn the adjuster 

CLOCKWISE

To INCREASE the operating time, turn the adjuster

 ANTI-CLOCKWISE

. Replace the fan terminal box cover.

 

 
 
 

~

N

L

1 Phase Supply

(220-240V 50Hz).

FUSE

L

LA

Fan

LB

3A

LS

N

REMOTE SWITCH

~

N

L

1 Phase Supply

(220-240V 50Hz).

FUSE

N

LA

Fan

LB

3A

10 - Basic Models 
 
 
 
 
 
 

 

For high speed operation wire into terminal 

LA

 for low speed wire into 

LB

 

N.B. If fan is used in conjunction with a Vent-Axia speed controller 

 the 

LA

 (High Speed) terminal 

MUST

 be used. 