Advanced Setup Table
cont. next page
Default = Factory Default Setting
Step# Description
Pg# Range
Default
1
Available Modes
25 Heat/Cool/Auto/Off,
Heat/Cool/
Heat/Cool/Off, Heat/Off,
Auto/Off
Cool/Off
2
Backlight
17 On, Off, 6pm-6am
Off
3
Backlight Level
17
Off thru 7 levels of brightness
Level 5
4
Night Dimmer
17 On/Off
Off
5
Night Dimmer Brightness
17
Off thru 7 levels of brightness
2 (20%)
6
Night Dimmer Start Time
17 12A-12A
8:00P
7
Night Dimmer Stop Time
17 12A-12A
6:00A
8
Current Service Filter Runtime Hours 23 0-1999 Hours
0
9
Current Service Filter Calendar Days 23 0-720 Days
0
10
Current Override Hours
7
0-1999 Hours
0
11
Current UV Lamp Calendar Days
24 0-720 Days
0
12
Current Humidifier Calendar Days
24 0-720 Days
0
13
Set Service Filter Runtime Hours
23 0-1950 hours
0
14
Set Service Filter Calendar Days
23 0-720 Days
0
15
Set UV Lamp Calendar Days
24 0-720 Days
0
16
Set Humidifier Calendar Days
24 0-720 Days
0
17
Language
17 English, Espanol, Francais English
18
Scrolling Method
18 “L-R Slow, L-R Fast,
Word L-R Slow, Word L-R
English
Fast, Whole Word L Slow,
Whole Word R Slow,
Whole Word Ctr. Fast,
Whole Word Ctr. Slow”
19
Setpoint Limits
26 No, Use
No
20
Max Heat Setpoint
26 35 - 99 Degrees
74
21
Min Cool Setpoint
26 35 - 99 Degrees
70
22
Cycles Per Hour
26 No Limit, 2, 3, 4, 5, 6
6
23
Compressor Minimum Off Minutes
26 0, 3, 5 Minutes
5
24
Min. Heat/Cool Setpoint Difference
26 0 - 6 Degrees
2
25
Number of Heat Stages
26 0 - 2
2
26
Number of Cool Stages
26 0 - 2
1
27
Number Of Compressor Stages
26 1, 2
1
28
Number of Aux Stages
26 0, 1, 2
0
29
1st Stage Deadband
27 1 - 6 Degrees
2
30
Wired Sensor Type
29 Remote, Supply
Remote
31
Control to Temp Source
30
Thermostat, Remote, Average
Thermostat
32
Humidity Only With Heat
28 On, Off
Off
33
Fan With Humidity Demand
28 Fan On, Fan Off
Fan Off