OUTDOOR LOCATION      The Outdoor Sensor should be mounted on the north side of the building, out of direct sunlight, 
and in a place that is protected from direct rain and snow.   Mounting the sensor under an eave of a roof or under an 
overhang of a building is recommended.

INDOOR LOCATION           The Outdoor Sensor should be mounted approximately five feet from the floor, close to or in a 
frequently used room, preferably on an inside partitioning wall or on a section of wall without pipes or ductwork.  Mount 
the sensor where temperature operating limits are within 32 to 99 F and where humidity operating range is within 0 to 95% 
relative humidity, non-condensing. 

INCORRECT LOCATIONS      The Outdoor Sensor should 

NOT

 be mounted close to a window, on an outside wall, or next 

to a door leading to the outside.  Do not mount the sensor in a location where it would be exposed to direct light and heat 
from a lamp, the sun, a fireplace, or any other temperature-radiating object which may cause a false reading.  Finally, do 
not mount the sensor close to or in direct airflow from supply registers or return air grilles and in areas with poor air 
circulation (such as behind a door or in an alcove).

IMPORTANT:  READ ALL OF THESE INSTRUCTIONS BEFORE INSTALLING THE SENSOR.

DIGITAL OUTDOOR

TEMPERATURE SENSOR

Sensor Location

Wiring Requirements

CAT 5 Cable

Thermostat Cable

The 

Sensor should be connected to the thermostat using solid conductor CAT 5, CAT 5e, or CAT 6 type network 

communication cable. This is an unshielded cable with four twisted pairs of 24 gauge solid wire; 

DO NOT use stranded 

cable

.  The cable length should not exceed 250 feet.  If less than 75 feet of cable is required to connect the thermostat to 

the Outdoor Sensor, a three conductor thermostat cable (18-24 gauge) may be used; this cable is NOT suitable for any 
length greater than 75 feet.

IMPORTANT:   Do no use shielded wire.   Do not run sensor wiring in the same conduit as the 24VAC thermostat wiring.   
Electrical interference may cause the sensor to give incorrect temperature readings.

Outdoor 

NOTE:  All sensor wiring must be in compliance with all applicable local and national codes.

SAFETY CONSIDERATIONS

Read  and  follow  the  manufacturer  instructions  carefully.    All  wiring  must  conform  to  local  and  national 
electrical codes.  Improper wiring or installation may damage the sensor.

Recognize safety information.  This is the safety alert symbol       .  When the safety alert symbol is present on 
equipment or in the instruction manual, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAUTION.  These words are used with the safety alert 
symbol.   DANGER identifies the most serious hazards which will result in severe personal injury or death.   
WARNING signifies a hazard which could result in personal injury or death.   CAUTION is used to identify 
unsafe practices which may result in minor personal injury or property damage.  

The Outdoor Sensor measures indoor or outdoor air temperature with a range of -40  to 127  F.  If used indoors 
as  a  remote  temperature  sensor,  the  sensor  will  read  room  temperature  and  send  the  information  to  the 
thermostat.    If  used  as  an  outdoor  temperature  sensor,  the  sensor  may  be  used  to  provide  outdoor 
temperature information (which is not used to control heating or cooling).

GENERAL

©Venstar Inc. 08/07          

P/N 88-623     Rev. 1

ACC0400