TECHNICAL MANUAL
6
TAMPER CONNECTION (ANTI-OPENING AND ANTI-FOAM)
Connect terminals no. 7 and no. 8 to the tamper line coming from the control panel.
LED COMMANDS
TERMINALS:
A
=RED,
B
=GREEN,
C
=BLUE,
D
=WHITE
A, B, C, D terminals control indipendently the flashing unit to run customisable notifications. Use DIP 8 to set
functioning.
DIP-SWITCHES
NOTE
: Dip switches setting is stored after 12 hours from the first supply. Take away and give again power to the
board to change settings.
DIP 1 SOUND TIMING
• Dip-switch 1 in OFF: sound timing is 3 minutes (DEFAULT SETTING).
• Dip-switch 1 in ON: sound timing is 8 minutes.
DIP 2 SOUNDER CONTROL INPUT POLARITY
NOTE: THE INPUT IS MISSING
• Dip-switch 2 in OFF: trigger for sounder activation is positive (DEFAULT SETTING).
• Dip-switch 2 in ON: trigger for sounder activation is negative.
DIP 3 SOUND TYPE SELECTION
• Dip-switch 3 in OFF: sound is INCREASING-CONTINUOUS-DECREASING-CONTINUOUS (DEFAULT SETTING).
• Dip-switch 3 in ON: sound is INCREASING-DECREASING.
DIP 4 SYSTEM STATUS OPTICAL SIGNALISATION (ON-OFF IMMEDIATE AND PERMANENT)
• Dip-switch 4 in OFF: instantaneous ON-OFF situation (DEFAULT SETTING).
• Dip-switch 4 in ON: instantaneous ON-OFF situation with blue LED flashing intermittently while trigger is given
to terminal 4.
By giving a command to terminal no.4, the LEDs of the sounder blink in red 3 times (ON) and all anomalies are
reset to zero. By taking command away, the LEDs light up steady in green for 5 seconds (OFF).
DIP 5 INPUT POLARITY 4 - 5 - A - B - C - D
NOTE: INPUTS ARE GIVING
• Dip-switch 5 in OFF: command is positive (DEFAULT SETTING).
• Dip-switch 5 in ON: command is negative.
DIP 6 INPUT 5 FUNCTION
• Dip-switch 6 in OFF: input 5 with block speaker function (DEFAULT SETTING).
• Dip-switch 6 in ON: input 5 with flash reset function. The flash starts withs the trigger and stops with the reset.
DIP 7 DAILY ALARM COUNTING
• Dip switch 7 in OFF: infinite alarms (default setting)
• Dip switch 7 in ON: max 4 alarms every 24h. Alarm is counted if it lasts at least 30 seconds. From 5th alarm, the
sounder flashes with no sound. System status activation resets alarm counting.