background image

Counterbalance Adjustment 

Procedure

The following instructions should be followed when 
attempting to maximize the counterbalance effect 
on the EM or GM model dampers. Be aware that 
when the balance setting is highly sensitive, friction 
wear, and contamination will have an adverse effect 
to the operation of the damper. The sensitivity of 
the counterbalance should only be set to meet the 
application requirements. The damper must be mounted 
square and plumb and operate freely before any weight 
adjustments are performed.

Counterbalance Adjustment for EM/

ES/GM-30, 31, and 32 Models: Vertical 

Mount - Horizontal Airflow

There are two different adjustments that can be made:
 

 Adjustment #1: affects the balance of the 
blades in the open position. Use this adjustment 
method if the damper blades do not achieve full 
open position under airflow and you want them 
to open further or all the way.    

 

 Adjustment #2: affects the balance of the blades 
in the closed position along with a small change 
to the open position balance.

If the airflow through the damper is light and the blades 
only slightly move from the closed position, then 
Adjustment #1 and #2 are required.

Adjustment #2: Balance the Blades in the Closed 
Position

The damper is assembled with the counterbalance 
weights and bracket installed such that, when the 
blades are closed, the counterbalance weights and 
bracket are positioned directly in-line with the blade 
pivot points. This position of the weights will provide a 
light load that will hold the blades in the closed position. 
To reduce this load, the counterweight mounting 
brackets can be bent away from the adjacent blade 
surface. Bending the counterweight mounting brackets 
will move the counterweight stack behind the blade 
pivot point and therefore allow the blades to start 
opening at lower airflow rates. This adjustment should 
be performed in small increments since the blades will 
not fully close if the brackets are bent too far. 

Adjustment #1:Balance the Blades in the Open 
Position

Moving the weight stack along the length of the 
mounting bracket slot will affect the full open balance 
of the blade assembly. Moving the weights further 
away from the blade pivot point will cause the blades 
to become more balanced so that at some point, and 
with enough weight, the blades would remain open. 
Care must be taken to ensure that when the weights 
are moved outward from the blade pivot point they will 
not interfere with the adjacent blade when the blades 
close. Moving the weights back towards the blade pivot 
point will allow the blades to close. If the damper blades 
do not open completely and Adjustment #1 has been 
addressed, then more weight is required.

4)  Damper must be installed into duct or opening square 

and free of twist or other misalignment. Damper 
must not be squeezed or stretched into duct or 
opening. Out of square, racked, twisted or misaligned 
installations can cause excessive leakage and/or 
torque requirements to exceed damper/actuator 
design.

5)  Damper and actuator must be kept clean, dry and 

protected from dirt, dust and other foreign materials 
prior to and after installation. Examples of such 
foreign materials include but are not limited to:

 

a) 

Mortar dust

 

b) 

Drywall dust

 

c) 

Firesafing materials

 

d) 

Wall texture

 

e) 

Paint overspray

6)  Damper should be sufficiently covered as to prevent 

overspray if wall texturing or spray painting will 
be performed within 5 feet (1.50m) of the damper. 
Excessive dirt or foreign material deposits on 
damper can cause excessive leakage and/or torque 
requirements to exceed damper/actuator design.

7)  ACCESS: Suitable access (actuators maintenance, 

etc.) must be provided for damper inspection and 
servicing. Where it is not possible to achieve sufficient 
size access, it will be necessary to install a removable 
section of duct.

Bend counterweight mounting 
bracket away from blades.

Bend Here

ES EM GM Series

2

Reviews: