- 20 -
User Manual - ADR-D 400 D90
English
INSTALLATION
WIRING DIAGRAM
L1
N
L2
L3
LOAD
NOTE:
Connection of the neutral conductor may ONLY be omitted for balanced
symmetrical three-phase systems
INSTALLATION
Network analyzer ADR D 400 D90 may only be used in three-phase systems 230 Vac
Phase-neutral, with 400 Vac Phase-Phase voltage between lines.
For installation, follow the connection diagram shown above:
− for 4-wire three-phase systems (3 neutral) also with non-symmetrical and/
or non-balanced systems, connect the neutral lead to terminal 1
− for 3-wire three-phase symmetrical and balanced systems, it is possible not to
connect the neutral lead
For correct measurement, the 3 phase leads coming from the distribution panel must
be inserted in the through holes vertically from above; failure to do so will cause a
connection-error warning to appear on the display. In case of a connection error, the
display will indicate which phase or phases are misconnected (cfr. “ERROR MESSAGES
– MISCONNECTION” ).