Velocity VL-SLC Installation Instructions Manual Download Page 6

 

 

                         
www.velocitydetection.com                            Doc:    GLT-294-7-2                    Issue: 001                              Date: 04/03/20

 

 

Front Unit LED Indications 

LED Indication 

Description 

Wire Break + (Yellow) 

Illuminated yellow when a loop break on the positive line is detected. 

Wire Break - (Yellow) 

Illuminated yellow when a loop break on the negative line is detected. 

Short A (Yellow) 

Illuminated yellow when a short circuit on the loop A side is detected. 

Short B (Yellow) 

Illuminated yellow when a short circuit on the loop B side is detected. 

Loop TX (Green) 

Flashing green when the loop card is transmitting information. 

Loop RX (Green) 

Flashing green when the loop card is receiving information. 

Com. (Green) 

Pulses to show communication between the module and the motherboard. 

 

Specifications 

Specification 

VL-SLC 

Part Number 

62-400 

Design Standard 

UL864 10

th

 Edition 

Approval 

UL Laboratories 

Rated Voltage 

35VDC Nominal (24V  - 39V) 

Maximum SLC Current 

200mA 

500mA 

Maximum SLC Resistance 

50Ω (25Ω per core) 

20Ω (10Ω per core) 

Maximum SLC Capacity 

254 Addresses 

Maximum SLC Cable Length 

*2KM 

Maximum SLC Capacitance 

100nF 

Maximum SLC Baud Rate 

4334 bits per second (typical) 

Maximum Ground Fault Impedance 

10KΩ 

Wiring Class 

Class X or Class A [Power limited & Supervised] 

Operating Temperature 

0°C (32°F) to 49°C (120°F) 

Max Humidity 

93% Non-Condensing 

Size (mm) (HxWxD) 

105mm x 57mm x 47mm 

Weight 

0.15KG 

Recommended Cable Sizes 

18 AWG to 14 AWG (0.8mm

2

 to 2.5mm

2

*Depending on what cable size is used. A 2KM maximum SLC distance is assuming 2.5mm

(14AWG) cables is used

.

 

 

Compatible Devices/Accessories 

Model No. 

Description 

VDOT-PY 

Addressable Photoelectric Smoke Detector  

VDOT-PY/7 

Addressable Photoelectric Smoke Detector 

(UL 268 7

th

 edition)

 

VDOT-PYH 

Addressable Multisensory Detector 

VDOT-PYH/7 

Addressable Multisensory Detector 

(UL 268 7

th

 edition)

 

VDOT-H2 

Addressable Heat Detector 

VDOT-H2-H 

Addressable High Temperature Heat Detector 

VDOT-DPH 

Addressable Dual Optical/Heat Detector 

VDOT-MiniIP 

Addressable Mini Input Module 

VDOT-DIP-SCI 

Addressable Dual Input Module with SCI 

VDOT-DOP-SCI 

Addressable Relay Dual Output with SCI 

VDOT-DOP-AC240V-SCI 

Addressable Relay Dual Output Module for AC240v with SCI 

VDOT-ZMU 

Addressable Conventional Zone Module with SCI 

Summary of Contents for VL-SLC

Page 1: ...vices have been installed on the loop Installation The MMP panel uses the expansion port number to reference modules It is recommended that any SLC modules are fitted first to the first expansion port...

Page 2: ...cure In addition the MMP panel is supplied with Din rail stoppers These should be fitted before the first module and after the last module on each rail Before Powering the Panel On 1 To prevent the ri...

Page 3: ...modules are fitted and that all module cables are correctly inserted Note that the panel will need at least one module fitted to run The panel has detected a new module added to a port that was previ...

Page 4: ...panel will report them as removed lighting the yellow Trouble LED intermittently sounding the trouble buzzer and displaying battery removed message on the screen 4 Connect the batteries ensuring that...

Page 5: ...ween isolator modules for Class X wiring Manual stations should be fitted between isolator modules Note If an SLC using Class A wiring is used for 2 or more detection zones short circuit isolators or...

Page 6: ...m SLC Cable Length 2KM Maximum SLC Capacitance 100nF Maximum SLC Baud Rate 4334 bits per second typical Maximum Ground Fault Impedance 10K Wiring Class Class X or Class A Power limited Supervised Oper...

Page 7: ...dressable Sounder Base VDOT SCI Short Circuit Isolator VDOT STB RL Low Power Relay Base VDOT STB SCI Short Circuit Isolator Base VDOT UB4 Standard Detector Mounting 4 Base VDOT UB4 6 Standard Detector...

Reviews: