Velocity VDOT-STB-SCI Manual Download Page 2

   

  Distributed By

http://www.velocitydetection.com

GLT-299-6-8

Rev.0

Zeta Alarms Limited 

72-78 Morfa Road, Swansea 

SA1 2EN 

Tel: +44 1792 455 175 FAX: +44 1792 455 176

All specifications are subject to change without any notice.

 

For more information, contact with VELOCITY.

Locking Screw

VDOT-STB-SCI contains a locking screw to avoid 

unauthorizedremoval of detectors.

 

Mounting

VDOT-STB-SCI can be mounted to a 3-1/2” octagonal elec-

trical box, or to a 4” square or a 4” octagonal electrical 

box when using a STBA-ADP optional mounting adaptor.

 

ƒ

Specifications

Specifications

VDOT-STB-SCI

SLC Applied Voltage

Rated Range 20 VDC to 38 VDC

SLC Current Consumption

Standby: 100 μA Activated (SCI Isolation): 22mA

SCI On Resistance

0.2 ohms (max)

SCI Fault Detection Voltage

10 V (min)

LED Visual Indicator

Short Circuit - Solid Yellow LED

Operating Temperature

-10°C to +83°C (14°F to 181.4°F)

Storage Temperature

-20°C to +60°C (-4°F to 140°F)

Relative Humidity

≤ RH 95 % non-condensing

Environment

Indoor, dry use only

Terminal

AWG12-22

Dimensions

φ104 mm x H 15 mm 

Weight

65 g

Standard

UL268 and UL521

 

Page 2

 

ƒ

Installation Diagrams

Analog Addressable Wiring 

When connected to analog addressable detectors such as 

VDOT-PY, VDOT-PYH, VDOT-H2, VDOT-DPH, etc.

Terminals 

VDOT-STB-SCI base is supplied with 3 terminals as follows: