13
FIGURE 5.6: BASIC DOMESTIC WATER PIPING
WARNING
If IWH is replacing a tankless coil, drain tankless coil and leave open to atmosphere. Do not plug coil.
Model
Max Boiler Water Limit Setting
220°F or Less
221° - 250°F
MS2-030
100,000
112,300
MS2-040
100,000
133,700
MS2-050
100,000
156,300
MS2-075
115,000
195,600
MS2-119
199,900
Note 1
1. Not permitted unless the combined output of all boilers
connected to this indirect water heater is less than 200,000
BTU/hr. If this condition is met, install a T&P valve having a
capacity of 200,000 BTU/hr.
2. Maximum T&P Valve Pressure Setting - 150 psi
3. Maximum T&P Valve Pressure Setting - 210°F
TABLE 5.7: MINIMUM T&P VALVE CAPACITY REQUIREMENTS (BTU/hr)