DAP Jumper (Direct Access to Programming)
If the Personal Master Code is forgotten, use the DAP jumper to override the forgotten code permitting direct entry
into programming mode. You are required to apply the following procedure precisely:
1. Disconnect power supply
2. Displace the DAP jumper from OFF to ON position.
3. Reconnect power supply (buzzer is activated).
4. Put the DAP jumper back to OFF position (this done, the buzzer is de-activated).
5. The Keypad is in programming mode and ready to receive your new programming data.
6. Enter the new programming data starting from Section
(B)
in the summary chart shown below.
5.
Programming the Keypad – Summary Chart
A) Use the factory set Master Code entry in programming -- When starting for first time only
Entry of Code
Validation
Comments
0000
*
Enter in programming mode by factory set master code
B) Programming -- Recording of personal master code & user codes -- User programming
Access Keys
Entry of Codes
Validation Comments
0
From 1 to 8 Digits
#
Personal Master Code & Super User Code
1
From 1 to 8 Digits
#
User Code 1 & Duress Code
( Suggest for door strike )
2
From 1 to 8 Digits
#
User Code 2 ( Suggest for alarm control )
3
From 1 to 8 Digits
#
User Code 3 (Suggest for alarm or auxiliary
control)
C) Programming -- Configuration of relay outputs -- Installer programming
Access Keys
Code Duration
(Seconds)
Validation Comments
4 0
From 1 to 999
#
Output 1 in MOMENTARY mode from 1 to 999 seconds (*)
4 1
/
#
Output 1 in START/STOP mode without accelerated code
(*).
4 2
/
#
Output 1 in START/ STOP mode with accelerated code (*).
5 0
From 1 to 999
#
Output 2 in MOMENTARY mode from 1 to 999 seconds
5 1
/
#
Output 2 in START/STOP mode without accelerated code.
5 2
/
#
Output 2 in START/ STOP mode with accelerated code.
6 0
From 1 to 999
#
Output 3 in MOMENTARY mode from 1 to 999 seconds
6 1
/
#
Output 3 in START/STOP mode without accelerated code.
6 2
/
#
Output 3 in START/ STOP mode with accelerated code.
(*) Auto re-lock is possible, see "DOOR N.C." for details.
D) Programming -- Safety -- Installer Programming
Access Keys
Validation
Comments
7 0
#
After 10 successive false codes, the keypad locks during 30 seconds.
7 1
#
After 10 successive false codes, the DURESS output is switching to
ground.
7 2
#
Disappearance of the 2 above securities.
E) Leave programming mode
Validation
Comments
*
The keypad leaves programming mode, and is in OPERATION mode, ready for daily use.