- 1 -
1981-R2 06/07
P/N 09-1034
© 2007 Velcon Filters, Inc.
VF-61UL
INSTRUCTIONS
1210 Garden of the Gods Rd., Colorado Springs, CO 80907
Phone: (719) 531-5855 FAX: (719) 531-5690
e-mail: [email protected] / web site: www.velcon.com
*****CAUTION!*****
To protect the fuel system, including the VF-61UL and
other components, be sure to install pressure relief valve(s).
DESCRIPTION
The Velcon VF-61UL filter housing is designed to operate with various
Aquacon
®
or microfilter
elements in diesel fuel applications. The filter housing is shipped with
no cartridge
installed.
Cartridges
must be ordered separately.
The VF-61UL vessel only (no cartridges) is
Underwriters Laboratory
Approved
under Component Listing.
Connections Size: 1-
1
/
2
" Female NPT
Housing Pressure Rating: 150 psi
NOTE:
FOR LIQUID SERVICE ONLY.
Do not use or leak test this filter vessel with compressed
air or other gases.
MODEL
DEGREE OF
COLLAPSE
TYPE
NUMBER
FILTRATION
STRENGTH
PLEATED MEDIA
FO-512PL
1
/
2
1
/
2
MICRON
75 psi
(Dirt Removal Only)
FO-512PL05
5 MICRON
75 psi
FO-512PL25
25 MICRON
75 psi
Aquacon
®
MEDIA
AC-51205
5 MICRON
75 psi
(Dirt and Water
Removal)
AD-51225
25 MICRON
75 psi
CARTRIDGE SELECTION